INSP-Final Inspection | 1/15/2013 | 1/16/2013 | 1/16/2013 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
FIR-Aging Inspection | 1/9/2013 | 1/9/2013 | 1/15/2013 | | NR |
Troy Cobbley
|
|
|
|
FIR-Aging Inspection | 9/28/2012 | 9/28/2012 | 10/1/2012 | | NR |
Troy Cobbley
|
|
|
Forwarded information to Scott for further action.
|
FIR-Aging Inspection | 4/30/2012 | 4/30/2012 | 5/2/2012 | | NR |
Troy Cobbley
|
|
|
I spoke to Charlie and he is going to follow up on status.
|
FIR-Aging Inspection | 1/20/2012 | 1/20/2012 | 1/23/2012 | | NR |
Troy Cobbley
|
|
|
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
|
INSP-Conference | 5/5/2011 | 5/5/2011 | 5/5/2011 | P | DONE |
Troy Cobbley
|
|
|
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
|
FIR-Aging Inspection | 3/22/2011 | 3/22/2011 | 3/29/2011 | | NR |
Troy Cobbley
|
|
|
Per Brian with SImplex Charlie is working on getting the elevators done.
|
FIR-Aging Inspection | 12/15/2010 | 12/15/2010 | 12/16/2010 | | NR |
Troy Cobbley
|
|
|
Per Charlie this permit is on their list of permits to get inspected.
|
INSP-Final Inspection | 10/15/2010 | 10/15/2010 | 10/15/2010 | P | FAIL |
Troy Cobbley
|
|
|
No test was performed at this location. Plan modifications are needed since a hat/light does light up in the elevator car. Also no shunt trip has been provided for the heat detector to activate. There are also sprinkler heads at the top and bottom of the elevator shaft.
|