INSP-Final Inspection | 6/24/2015 | 6/26/2015 | 6/26/2015 | A | PASS |
Jim Page
|
|
|
Pre-action system tested, isolated low air alarm, no solenoid activation, isolated one smoke, no solenoid activated, activated low air with smoke, solenoid activated and tripped pre-action valve. Also tested alarm pressue switch as well as both tamper switches associated with this pre-action system.
|
FIR-Aging Inspection | 6/15/2015 | 6/15/2015 | 6/23/2015 | | NR |
Troy Cobbley
|
|
|
I spoke with St Als Maintenance, John Mcademis, about the need to get this inspection performed.
|
INSP-Final Inspection | 6/22/2015 | 6/22/2015 | 6/22/2015 | P | CANC |
Troy Cobbley
|
|
|
I set up wrong inspection number
|
FIR-Aging Inspection | 4/29/2014 | 4/29/2014 | 5/7/2014 | | NR |
Troy Cobbley
|
|
|
I spoke to Brian about getting this permit finaled
|
FIR-Aging Inspection | 5/31/2013 | 5/31/2013 | 6/4/2013 | | NR |
Troy Cobbley
|
|
|
I spoke to Curtis at SimplexGrinnell and he is going to follow up with Charlie and Steve on the job status.
|
FIR-Aging Inspection | 1/21/2013 | 1/21/2013 | 1/24/2013 | | NR |
Troy Cobbley
|
|
|
Brian with SimplexGrinnell is going to follow up on the project status.
|
FIR-Aging Inspection | 9/28/2012 | 9/28/2012 | 10/1/2012 | | NR |
Troy Cobbley
|
|
|
Forwarded information to Scott for further action.
|
FIR-Aging Inspection | 3/20/2012 | 3/20/2012 | 3/20/2012 | | NR |
Troy Cobbley
|
|
|
I spoke to Charlie with SimplexGrinnel and he stated he would follow up on this project.
|