Permit Information
Permit NumberFIR11-00195
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1150 N CURTIS RD
Project NameBureau of Reclamation
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of recalculating the sprinkler system and changing piping to accommodate high piled rack storage. The existing 3” riser will be changed to a 4” riser.


Location on Plan - Various location
Commodity - Paper records and office equipment
Classification - Class III
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - >8’
Height of Storage - 15’
Ceiling Height - 24’ but there is a large steel mezzanine
Encapsulated - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - SSU Large Orifice
High Temperature Sprinklers Required - Yes
NFPA Section - T 16.2.1.3.2, 16.2.1.3.2(c), F 16.2.1.3.4.1, T 16.2.1.3.5
Fire Protection Requirements - .222/2000 + 500 Hose


Building Department Scope:

At this time, there is no associated building permit or racking permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/22/20156/22/20156/22/2015PPASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection6/16/20156/16/20156/22/2015 PASS
DetailsTroy Cobbley
FIR-Aging Inspection2/20/20132/20/20132/28/2013 DEFR
DetailsTroy Cobbley
I contacted Roy in Fire Prevention and he is going to follow up with the owner.
INSP-Conference10/10/201210/10/201210/10/2012PDONE
DetailsTroy Cobbley
I met with Steve, with the BLM, and we verified that the solid shelving had been removed and that the storage had been reduce to 15'-0". A racking permit is still required. I defered him to plan review for further information on this permit due to his engineer stating that a permit should not be required. Sent email to Scott.
FIR-Aging Inspection10/5/201210/5/201210/10/2012 NR
DetailsTroy Cobbley
See conference notes
FIR-Aging Inspection3/13/20123/13/20123/20/2012 NR
DetailsTroy Cobbley
I spoke to Charlie with SimplexGrinnel and he stated he would follow up on this project.
INSP-Sprinkler Rough-in/Hydro5/24/20115/25/20115/25/2011PPART
DetailsTroy Cobbley
The overhead hydro and sprinkler rough-in passed. The plans are approved for max. storage height of 15'. The current storage height is 17' and solid shelving with 2x4 supports are being utilized. So the storage arrangement needs to be permanantly modified or resubmittals are required. Also the project can not be finaled until a racking permit is applied for.