Permit Information
Permit NumberFIR13-00182
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 8055 W GODDARD RD
Project NameCapital High Hallway Renovatio
Customer Number 
ePlanReviewYes
Description
This fire alarm permit is to upgrade the corridors and the gymnasium to meet current code requirements per a previous agreement. This scope of work includes horn/strobe notification in the corridors and speaker/strobe voice evacuation in the gymnasium, smoke detectors, heat detectors, releasing magnetic door holders, pull stations, new remote power supplies, run circuiting to prepare for future deletion of the existing amplifier, provide circuiting to eventually switch over to IDnet devices. A new transponder will serve the gymnasium initiating devices.
Associated building permit: BLD12-03211
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/22/20138/22/20138/22/2013PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing8/20/20138/21/20138/21/2013ADONE
DetailsTroy Cobbley
Provide map at the facp and NFPA 72 forms
INSP-Final Inspection8/20/20138/21/20138/21/2013AFAIL
DetailsTroy Cobbley
Provide map at the facp and NFPA 72 forms.
INSP-Alarm Testing8/14/20138/20/20138/20/2013ACANC
DetailsTroy Cobbley
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Tuesday, August 20, 2013.
INSP-Alarm Testing8/14/20138/19/20138/19/2013ACANC
DetailsTroy Cobbley
To be rescheduled per Brian for thursday.
INSP-Alarm Testing8/14/20138/16/20138/16/2013ADONE
DetailsTroy Cobbley
Items needing correction for a final sign off on this permit are to increase the candella of select corridor strobes to provide coverage at the second floor stairwells and provide coverage as dicussed at the double doors where strobe coverage exceeds 15'. Also need to set off horn/strobes to verify functionality and sync.
INSP-Alarm Testing7/17/20137/19/20137/19/2013ADONE
DetailsTroy Cobbley
Completed the Gym Area which included corridors and dressing rooms. Corrections have been made as noted on the previous correction notice. However it appears notification is missing from a small restroom as noted on the plans.
INSP-Alarm Testing7/17/20137/18/20137/18/2013ADONE
DetailsTroy Cobbley
To days inspection was for the gym area. See the city approved plans for detectors marked "ok" that have been tested. I noted two smoke detectors that will need to be added on the mezzanine level. Also one strobe on the gym floor level that is overspaced from a wall.