INSP-Final Inspection | 7/15/2019 | 7/15/2019 | 7/15/2019 | P | PASS |
Troy Cobbley
|
|
|
Ok to final per Jim Page. I witnessed the testing of the fire sprinkler device interconnection with the fire alarm system.
we would like to perform this in conjunction with fire alarm. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
INSP-Final Inspection | 6/1/2016 | 6/1/2016 | 6/1/2016 | P | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with point of contact, Adam phone number ###-####, fire sprinkler system is not monitored, final inspection cannot be completed until fire sprinkler monitoring is provided by building owner and fire sprinkler alarm signals are verified with monitoring company.
|
INSP-Sprinkler Rough-in/Hydro | 3/30/2016 | 3/30/2016 | 3/30/2016 | P | PASS |
Jim Page
|
|
|
Hydrostatic test for underground piping complete, contractor disconnected underground from provided water source and tested the underground that was installed by the sprinkler contractor, hydrostatic test passed once it was disconnected from water source, capped and tested by itself.
|
INSP-Final Inspection | 3/30/2016 | 3/30/2016 | 3/30/2016 | P | CANC |
Jim Page
|
|
|
This inspection request cancelled, request is for underground hydrstatic test, new inspection will be generated.
|
INSP-Sprinkler Rough-in/Hydro | 3/23/2016 | 3/23/2016 | 3/23/2016 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with Adam Phone #: ###-####, underground would not hold pressure, underground hydrostatic test will be rescheduled after repair is made.
|
INSP-Supply line flush | 3/22/2016 | 3/22/2016 | 3/22/2016 | P | DONE |
Jim Page
|
|
|
Underground main line flush complete
|
INSP-Final Inspection | 3/3/2016 | 3/3/2016 | 3/3/2016 | P | PASS |
Jim Page
|
|
|
Hydrostatic test, 2 hours @ 200 psi passed/complete for overhead sprinkler piping
|
INSP-Sprinkler Rough-in | 2/29/2016 | 2/29/2016 | 2/29/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection complete for uderground supply, approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 2/22/2016 | 2/22/2016 | 2/22/2016 | P | PASS |
Jim Page
|
|
|
Overhead fire sprinkler rough to cover inspection complete, all area's approved for cover. Hydrostatic test to be completed at later date.
|