Permit Information
Permit NumberFIR16-00443
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 7943 W PREECE DR
Project NameTowne Pointe Apts Bldg E
Customer Number 
ePlanReviewYes
Description
[Towne Point Apartments Building E]
The fire sprinkler scope of work consists of protecting a two level NFPA 13 R four-plex. CPVC piping and extended coverage residential sprinklers are being utilized.

[BLD16-01108] - For building area and to eliminate the requirement to rate the exterior walls building E & F are considered one building. Permit for the construction of a new 2 story 4,288 sq. ft. four plex all of which are two story units with each having their own entries. Construction will be wood framed type VB construction. All work per the approved plans attached engineering and any notations. This building is fully fire sprinklered for R occupancy. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/4/201611/4/201611/4/2016APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection11/2/201611/3/201611/3/2016ACANC
DetailsTroy Cobbley
Jim Danes is contact. Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in/Hydro11/2/201611/3/201611/2/2016ACANC
DetailsTroy Cobbley
Jim Danes is contact. Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
INSP-Final Inspection11/1/201611/2/201611/2/2016AFAIL
DetailsTroy Cobbley
Needed an above ground hydro test which passed. Final to be rescheduled for tomorrow morning.
INSP-Sprinkler Rough-in/Hydro11/1/201611/1/201611/1/2016PPART
DetailsKatie Marron
When looking into riser room, riser on the right passed hydrostatic test satisfactory. Riser on the left dropped 2-3 psi, will need to be rehydro'd.
INSP-Sprinkler Rough-in9/9/20169/12/20169/12/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. Tenting inspection complete for overhead fire sprinkler piping located in attic spaces, overhead fire sprinkler pipe tenting approved for cover. Fire sprinkler heads in upstairs closets are located less than 24 inches away from heat register (fire sprinkler heads were ordinary temperature heads at time of this inspection). NFPA 13R requires ordinary temperature heads to be 24 inches from edge of heat source, 12 inches away for intermediate temperature heads, (NFPA 13R, Table 6.2.3.3.3) fire sprinkler heads will need to be changed to intermediate temperature and verified before final inspection. Fire sprinkler heads in main entry for all apartments have fire sprinkler heads that are less than 8 feet apart, NFPA 13R specifies a minimum of 8 feet between heads, the on site sprinkler contractor instructed that a surface mount light will be dividing the space between the 2 fire sprinkler heads, noted that distance of light below the deflector of the fire sprinkler head will need to be verified after light fixture is installed, if the light is not an obstruction then fire sprinkler heads will need to be relocated to code compliant of having a minimum of 8 feet between fire sprinkler heads.
INSP-Sprinkler Rough-in8/23/20168/24/20168/24/2016ACANC
DetailsTroy Cobbley
No approved drawings and per conversation it appears plans will need to be re-submitted.