Permit Number | FIR17-00027 |
Status | Finaled |
Name |
VIKING AUTOMATIC SPRINKLER CO
|
Site Address |
5710 S PAN AM AVE
|
Project Name | Sysco Food - Overflow Racking |
Customer Number | |
ePlanReview | Yes |
Description |
[Sysco Food - Overflow Racking]
The fire sprinkler scope of work consists of adding one row of in rack sprinklers,
Location on Plan -
Col 4 between Col C & E
Commodity -
Water filled bottles wrapped in plastic, canned Foods on cardboard wrapped in plastic and flour in paper bags in plastic
Classification -
Storage Type (rack, solid pile, etc.) -
Racks
Pallet Type (wood or plastic) -
Wood
Aisle Width -
One Row ONLY – No Aisle
Height of Storage -
22’
Ceiling Height -
25’-8”
Encapsulated -
No
Solid Shelves -
No
Smoke and Heat Vents -
No
Draft Curtain -
No
In Rack Sprinklers -
Yes
Sprinkler Type -
Existing 100 ft² .19/2009 (21) Flowing
High Temperature Sprinklers Required -
Yes
Applicable NFPA Section -
16.2.1.3.2(c) curve A or B
Hydraulic Design Criterion -
.245/2000
Hose Stream Requirements -
500
There does not seem to be an associated building permit at this time.
|