Permit Information
Permit NumberFIR18-00732
StatusFinaled
Name MOUNTAIN ALARM
Site Address 8601 W EMERALD ST
Project NameECP 8601
Customer Number 
ePlanReviewYes
Description
Replace existing Silent Knight 5207 FACP (obsolete) with new Silent Knight 5208 FACP. There does not appear to be an associated building permit.**Plan Mod** Add annunciators, pulls and flows in a manner that seperates signals from the individual buildings.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  6/13/2019 DONE
Final acceptance test passed 6-6-19 and as builts approved 6-13-19.
INSP-Final Inspection6/3/20196/4/20196/6/2019PFAIL
DetailsTroy Cobbley
Permit will be ok for final when as-builts are approved.

Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection3/26/20193/28/20193/28/2019AFAIL
DetailsTroy Cobbley
Resubmit plans that show entire scope of work that includes all devices in all buildings. Devices shall annunciate by the building address. Installation shall meet NFPA 72. Provide updated battery and notification circuit calculations. Separate remote annunciators maybe required for each building. Lightning protection may be required for circuits connecting each building. All buildings may require riser room pull stations. The horns on the exterior of the building may not be required.

Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection1/24/20191/30/20191/30/2019ACANC
DetailsTroy Cobbley
Cancel per Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection12/28/20181/4/20191/2/2019ACANC
DetailsTroy Cobbley
Ray McQueen, inspecting technician Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
INSP-Final Inspection10/4/201810/9/201810/8/2018ACANC
DetailsTroy Cobbley
Ray McQueen, inspecting technician, building access is open Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson