Permit Information
Permit NumberFIR19-00293
StatusFinaled
Name PROTEX
Site Address 5450 W GOWEN RD
Project NameKnife River Shop/Office
Customer Number 
ePlanReviewYes
Description
Add new fire panel to new construction for sprinkler monitoring and elevator recall. This work is associated with building permit BLD19-00101.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/18/201912/18/201912/18/2019PPASS
DetailsTroy Cobbley
Permit finaled.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection12/17/201912/17/201912/17/2019PCANC
DetailsTroy Cobbley
Phone lines have been cut. Inspection requested via web by Morgan Ahten
INSP-Alarm Testing12/10/201912/11/201912/11/2019ADONE
DetailsTroy Cobbley
Head end equipment and interconnection with the fire sprinkler devices tested. For a final sign off we need the phone line troubles to report in less than 200 seconds, need elevator recall tested and final documents. Knox box needs installed as well.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Alarm Testing12/10/201912/10/201912/10/2019PFAIL
DetailsTroy Cobbley
We were unable to test phone lines due to non-functioning testing equipment. Inspection stopped since I can not verify communication means.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten