INSP-Final Inspection | 5/11/2020 | 5/11/2020 | 5/11/2020 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
please call 1/2 hour prior Phone #: ###-#### Inspection requested via web by Rick Groom
|
INSP-Final Inspection | 5/4/2020 | 5/5/2020 | 5/5/2020 | P | FAIL |
Jim Page
|
|
|
No devices tested, horn strobes and pull stations from old fire alarm system are still in place, non-functioning fire alarm devices must be removed before final inspection can be completed, per installing contractor old devices in place are not integrated with the new fire alarm panel, also old devices are not compliant with the current NFPA72.
Please call 1/2hour prior Phone #: ###-#### Inspection requested via web by Rick Groom
|