Final | 2/11/2019 | 2/12/2019 | 2/12/2019 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Final | 2/7/2019 | 2/7/2019 | 2/7/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need to submit manual j with city for approval and have approved manual j onsite for final
|
Final | 2/6/2019 | 2/6/2019 | 2/6/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- equipment installed does not match manual j- need to resubmit to city and have approved manual j onsite for final inspection
|
Rough-in | 12/12/2018 | 12/13/2018 | 12/13/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- R/I ok
|
Pressure Test | 12/13/2018 | 12/13/2018 | 12/13/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 20lb gas pass test whole system ok
|
Rough-in | 12/12/2018 | 12/12/2018 | 12/12/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- insulation shield is not installed now- needs to be 7" round or bigger to maintain 1" clearance to b vent- need to retest gas line since it was rerouted at range to different location
|
Rough-in | 12/10/2018 | 12/11/2018 | 12/11/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need approved csst nail plates at ceiling both sides at range location- need to seal dryer duct to termination box- insulation shield needs minimum 1" clearance to b vent- left correction notice front entry window
|
Pressure Test | 12/10/2018 | 12/11/2018 | 12/11/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 20lb gas pass
|