Final | 3/8/2019 | 3/11/2019 | 3/11/2019 | A | PASS |
Brian Scoles
|
|
|
re inspection balance report is now on site Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 3/8/2019 | 3/11/2019 | 3/8/2019 | P | CANC |
Chad Schwendiman
|
|
|
re inspection Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|
Final | 3/7/2019 | 3/8/2019 | 3/8/2019 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- no air balance report onsite- need uv protection on lineset outside at a/c location
|
Conference | 1/31/2019 | 2/1/2019 | 2/1/2019 | A | PASS |
Brian Scoles
|
|
|
Witness bast inspection confirmed with Brian for 02/01/2019 @11:30AM Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test pass
|
Rough-in | 1/28/2019 | 1/29/2019 | 1/29/2019 | P | PASS |
Brian Scoles
|
|
|
re-inspection Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
|
Rough-in | 1/21/2019 | 1/28/2019 | 1/28/2019 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- Furnace coil in attic ok- need to insulate fresh air can in attic where ties onto R/A plenum bare metal- need to firecaulk b vent in chase 2nd floor at ceiling and floor- all exhaust fans need sealed under flex ducting where metal ties onto plastic fitting on fan(ongoing issue on R/I)- left correction notice front window
|
Pressure Test | 1/21/2019 | 1/28/2019 | 1/28/2019 | A | PASS |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged gas line at meter location
|