Final | 5/1/2019 | 5/2/2019 | 5/2/2019 | P | PASS |
Brian Scoles
|
|
|
GARAGE CODE IS 0425, OR 3484 Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
|
Final | 4/30/2019 | 4/30/2019 | 4/30/2019 | P | FAIL |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- need to rebalance air balance test closer to design cfm- to high
|
Rough-in | 3/5/2019 | 3/6/2019 | 3/6/2019 | P | PASS |
Brian Scoles
|
|
|
re-inspect. builder can not provide ladder. i can call 2089148354 when going to job site so we can meet you there. Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok- fireplace R/I ok
|
Rough-in | 3/6/2019 | 3/6/2019 | 3/6/2019 | P | PASS |
Brian Scoles
|
|
|
re-inspect. builder can not provide ladder. i can call 2089148354 when going to job site so we can meet you there. Phone #: ###-#### Inspection requested via web by Oleg Chervak- fireplace R/I ok
|
Pressure Test | 3/6/2019 | 3/6/2019 | 3/6/2019 | P | PASS |
Brian Scoles
|
|
|
re-inspect. builder can not provide ladder. i can call 2089148354 when going to job site so we can meet you there. Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass
|
Rough-in | 2/28/2019 | 3/4/2019 | 3/4/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- gas gauge at zero- need approved manual J onsite- need ladder provided by contractor to safely acces furnace in attic- fireplace inner thimble not installed per manufactures installation instructions-fresh air can not come from roof and needs to be tied into R/A plenum off furnace- left correction notice in back window
|
Pressure Test | 3/4/2019 | 3/4/2019 | 3/4/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- gauge at zero psi
|