Final | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | PASS |
Troy James
|
|
|
Please call Delroy at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Rough-in | 6/28/2019 | 7/1/2019 | 7/1/2019 | A | PASS |
Chad Schwendiman
|
|
|
Please call Delroy at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Final | 6/21/2019 | 6/24/2019 | 6/24/2019 | P | CANC |
Chad Schwendiman
|
|
|
Please call Delroy at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Not ready for a final, This should have been scheduled as a rough in
|
Rough-in | 6/24/2019 | 6/24/2019 | 6/24/2019 | P | FAIL |
Chad Schwendiman
|
|
|
Please call Delroy at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Make up air duct not sized per plans, Need a clear access space large enough for the removal of the air handler in the hard lid ceiling, Return duct for adjacent space is currently open into this space. Need to route it into adjacent space.
|
Rough-in | 6/19/2019 | 6/20/2019 | 6/20/2019 | P | FAIL |
Chad Schwendiman
|
|
|
Please contact Delroy at least 30 min prior to inspection, Thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum - need to install wrap on access door per manufactures installation instructions
|
Rough-in | 6/18/2019 | 6/19/2019 | 6/19/2019 | P | PART |
Chad Schwendiman
|
|
|
Please call Delroy at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 1st layer fire wrap okay
|
Rough-in | 6/18/2019 | 6/18/2019 | 6/18/2019 | P | PART |
Chad Schwendiman
|
|
|
Please call Delroy at least 30 min prior to inspection. He will be on sight until 2:30. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to install 1st layer of fire wrap on grease duct
|
Rough-in | 6/17/2019 | 6/17/2019 | 6/17/2019 | P | PART |
Chad Schwendiman
|
|
|
Please call Del at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum - light test on grease duct pass, Need to support grease duct to maintain grade, need gasket on access door
|
Rough-in | 5/15/2019 | 5/17/2019 | 5/17/2019 | A | PASS |
Ben Livingston
|
|
|
Please call Delroy at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|