Permit Information
Permit NumberMEC19-01716
StatusFinaled
Name YMC INC
Site Address 139 E WARM SPRINGS AVE
Project Name 
Customer Number2107791
ePlanReviewNo
Description
Addition: Furnish and install new HVAC equipment and accessories as required
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/31/20201/31/20201/31/2020PPASS
DetailsBen Livingston
Final1/30/20201/31/20201/31/2020AFAIL
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- Chad still hasnt recieved revised documentation -
Final1/28/20201/29/20201/29/2020AFAIL
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- need updated balance and commisioning reports for final -
Final12/18/201912/18/201912/19/2019PPART
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum


Items of concern:

F-112 unit undersized for CFM values shown on drawing (if the drawings are revised we will need the new drawings submitted so our documents are updated as well).
F-113 outdoor units needs to be repaired before unit can operate at high speed.
F-103 unit is oversized for the connected CFM load.
F-202 unit is only achieving 78% of designed air flow.
FC-101 and FC-115 Not operating.
Living room A201 missing balance dampers in 6 of the supply branch lines
No access to damper in dining room A154-
- temp C.O. okay -
Rough-in12/13/201912/16/201912/16/2019APASS
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- need uv protection on armaflex, and comisioning report approved for final -
Final11/21/201911/21/201911/21/2019PNR
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- armaflex needs uv protection -
- condencers need locking caps -
- all 2nd condensate drains on furnaces need tobe run -
- not all gardian systems on ranges are complete -
- industrial dryer vents need tobe supported -
- louver in laundryroom isnt wired up -
- need to submit commisioning report to Chad for approval -
Rough-in10/17/201910/17/201910/17/2019PPASS
DetailsBen Livingston
1st floor Area A. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- 1st floor above grid okay -
Rough-in7/15/20197/16/20197/16/2019APASS
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
-- area B 1st floor corridors and rooms above lids okay--
Rough-in7/11/20197/11/20197/11/2019PPASS
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
2nd floor area B restrooms
Rough-in7/9/20197/9/20197/9/2019PPASS
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
1st floor smoke dampers okay, guest rest room fans okay, all above lids 1st floor okay
Rough-in6/26/20196/26/20196/26/2019PPASS
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- kitchen and dinning room above lid okay-
Rough-in6/18/20196/19/20196/19/2019PPASS
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
-2nd fllor area A corridors, geust bathroom lids okay-
-2nd floor dryer vent walls NOT READY---
-1st floor area A section 1 restroom lids okay
Rough-in6/12/20196/13/20196/13/2019PPASS
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
2nd floor duct seal okay, 1st floor area B flue okay
Rough-in6/6/20196/7/20196/7/2019APART
DetailsBen Livingston
Please call Bryan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
-area A 1st floor soffits and restrooms okay
2nd floor fire smoke damper angles need to be tighter, clearance ok on 2
Rough-in5/31/20195/31/20195/31/2019PPART
DetailsBen Livingston
Please call Bryan at least 30 minutes prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
2nd floor area A zone 1 part duct seal okay
Rough-in5/9/20195/10/20195/10/2019APART
DetailsBen Livingston
Please call Bryan 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
flues 1st floor ceiling to 2nd floor attic