Final | 10/15/2019 | 10/16/2019 | 10/16/2019 | A | PASS |
Ben Livingston
|
|
|
Need a mechanical final and need to do a duct blast witness at 10am Phone #: ###-#### Inspection requested via web by Gary Reeves
|
Rough-in | 5/30/2019 | 5/31/2019 | 5/31/2019 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves 5lb flue x2 rough-in
|
Rough-in | 5/28/2019 | 5/29/2019 | 5/29/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves 1- dryer vent exceeds 35' max length 2- need access framed in for outside air for range mau to access damper in attic 3- missing 2 supply ducts in kitchen 4- missing transfer for office 5- w/h flue at zero
left correction n otice front entry window
|
Pressure Test | 5/28/2019 | 5/29/2019 | 5/29/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass
|
Rough-in | 5/24/2019 | 5/28/2019 | 5/28/2019 | P | CANC |
Ben Livingston
|
|
|
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
Pressure Test | 5/24/2019 | 5/28/2019 | 5/28/2019 | P | CANC |
Ben Livingston
|
|
|
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|