Final | 7/1/2019 | 7/5/2019 | 7/5/2019 | A | PASS |
Chad Schwendiman
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart
|
Rough-in | 5/23/2019 | 5/24/2019 | 5/24/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- fireplace and HVAC R/I ok
|
Pressure Test | 5/23/2019 | 5/24/2019 | 5/24/2019 | A | PASS |
Brian Scoles
|
|
|
Inspection requested via web by Randy Hart- 20lb gas pass
|
Rough-in | 5/22/2019 | 5/23/2019 | 5/23/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart 1- gas test failed at 13psi 2- need to insulate bare metal on supply plenums where round ties into square duct and all wye branch fittings in attic where bare metal showing to R-8 3- supply main to master bedroom needs 3 inch clearance to fireplace flue in attic 4- need ladder provided by contractor to access furnace/coil in attic 5- need to insulate filter box for outside air in attic where ties onto return plenum bare meatal showing 6- master bath exhaust in toilet room needs metal to plactic connection sealed at fan location
left correction notice front entry window
|
Pressure Test | 5/22/2019 | 5/23/2019 | 5/23/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- gas test failed gauge at 13psi
|
Pressure Test | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | NR |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart
|
Rough-in | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | NR |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart
|