Final | 7/24/2019 | 7/25/2019 | 7/25/2019 | A | PASS |
Brian Scoles
|
|
|
call around 10am to see if someone available- ###-####- furnace a/c coil co ok- corrections made
|
Final | 7/23/2019 | 7/24/2019 | 7/24/2019 | P | CANC |
Brian Scoles
|
|
|
INSPECTION FOR FURNACE/AC CHANGE OUT.
No one lives in the home. The homeowner''''s sister can come let you in. Please call her 30-60 minutes before inspection so she can let you in. Karen Hendrix, ###-#### Phone #: ###-#### Inspection requested via web by John Eastman- i rescheduled this for tomorrow am per phone call with tenant
|
Final | 7/15/2019 | 7/16/2019 | 7/16/2019 | P | FAIL |
Brian Scoles
|
|
|
INSPECTION FOR FURANCE/AC CHANGE OUT.
No one lives in the home. The homeowner''s sister can come let you in. Please call her 30-60 minutes before inspection so she can let you in. Karen Hendrix, ###-#### Phone #: ###-#### Inspection requested via web by John Eastman- need uv protection on lineset putside at a/c- need weather tight whip between disconnect and a/c- secondary drain needs wet switch in stalled- recall in when corrections are made
|
Final | 7/15/2019 | 7/16/2019 | 7/15/2019 | P | CANC |
Brian Scoles
|
|
|
Retro Change out Phone #: ###-#### >> Inspection requested via web by John Eastman Inspection cancelled from web by: John Eastman
|