Final | 1/17/2020 | 1/21/2020 | 1/21/2020 | A | PASS |
Chad Schwendiman
|
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen
|
Rough-in | 12/6/2019 | 12/6/2019 | 12/6/2019 | P | PASS |
Chad Schwendiman
|
|
|
Sealer 4th floor - Jerermy Phone #: ###-#### Inspection requested via web by Brandon Sorensen
|
Final | 11/14/2019 | 11/14/2019 | 11/14/2019 | P | PART |
Chad Schwendiman
|
|
|
partial final Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Phase 2 okay
|
Rough-in | 11/5/2019 | 11/6/2019 | 11/6/2019 | A | FAIL |
Chad Schwendiman
|
|
|
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Missing 1 support wire on 4' linner diffuser can in room 402. Missing supply grill in room 407
|
Rough-in | 10/24/2019 | 10/25/2019 | 10/25/2019 | A | PASS |
Chad Schwendiman
|
|
|
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Okay to cover phase 2 ceiling in open area
|
Rough-in | 10/23/2019 | 10/24/2019 | 10/24/2019 | A | FAIL |
Chad Schwendiman
|
|
|
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Need to add supports to the flex ducts currently supported by electrical conduits and plumbing pipes
|
Rough-in | 10/10/2019 | 10/11/2019 | 10/11/2019 | P | PASS |
Chad Schwendiman
|
|
|
sealer inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Okay to insulate duct work in phase 2
|
Rough-in | 9/13/2019 | 9/16/2019 | 9/16/2019 | P | PASS |
Chad Schwendiman
|
|
|
partial cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Okay to cover ceilings in phase 1
|
Rough-in | 9/11/2019 | 9/12/2019 | 9/12/2019 | A | FAIL |
Ben Livingston
|
|
|
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen - not all 24" slot diffusers have siesmic wires, there is an open 4" round duct above cieling -
|
Rough-in | 8/22/2019 | 8/23/2019 | 8/23/2019 | A | PASS |
Chad Schwendiman
|
|
|
sealer inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen
|