DOC - Permit Finaled | 6/13/2019 | 6/13/2019 | 6/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
As per 375 Eric Story notes Final ok
|
MIS-Aging Inspection | 6/13/2019 | 6/13/2019 | 6/13/2019 | | PASS |
Rock A. Hudson
|
|
|
See Final
|
ELE-Final | 6/13/2019 | 6/13/2019 | 6/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
As per 363 Final ok
|
MIS-Aging Inspection | 3/14/2019 | 3/14/2019 | 3/14/2019 | | PASS |
Rock A. Hudson
|
|
|
Defer for Eric Story, he is last to deal with this job.
|
MIS-Aging Inspection | 3/14/2019 | 3/14/2019 | 3/14/2019 | P | PASS |
Eric Story
|
|
|
All circuits were verfied and all RTU were installed under current codes and all checked out...
|
ELE-Conference | 6/11/2018 | 6/12/2018 | 6/12/2018 | A | FAIL |
Eric Story
|
|
|
Call Jack Reynolds MEC inspector ###-####. As of 6-11-18 3pm a electrical permit does not exist for 6 mini split units with corrections listed. However a new MEC permit exists for 21 new units at same address inspection scheduled AM 6-12-18. Stop work order in place and placed a double fee and no hold on address until a ELE is present
|
ELE-Conference | 6/4/2018 | 6/4/2018 | 6/4/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Call Jack Reynolds before you go out Phone #: ###-#### 210.63- A receptacle outlet shall be installed with in 25" of an HVAC unit. Roof east end. 300.15- All unused cables shall terminate in a box. Cable above bathroom ceilings shall be in a box. Disconnect unused wiring from over current devices. 440.6- Ampacities shall not exceed that posted on nameplate. Roof top minisplit units have max ampacity of 15 amp with 20 amp installed. Electrical contractor must pull permit and complete corrections. Will check back in 7 days for permit.
|