PLM-Aging Inspection | 12/27/2019 | 12/27/2019 | 12/27/2019 | | FAIL |
Matt Wrobel
|
|
|
permit expired
|
DOC - Permit Finaled | 12/27/2019 | 12/27/2019 | 12/27/2019 | P | PASS |
Matt Wrobel
|
|
|
permit expired
|
PLM-Aging Inspection | 9/27/2019 | 9/27/2019 | 9/27/2019 | | PART |
Matt Wrobel
|
|
|
no calls permit will expire next aging
|
PLM-Aging Inspection | 6/28/2019 | 6/28/2019 | 6/28/2019 | | PART |
Matt Wrobel
|
|
|
no calls
|
PLM-Aging Inspection | 3/29/2019 | 3/29/2019 | 3/29/2019 | | PART |
Matt Wrobel
|
|
|
left notice to call for inspection
|
PLM-Aging Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 | | NR |
Matt Wrobel
|
|
|
wip
|
PLM-Aging Inspection | 9/28/2018 | 9/28/2018 | 9/28/2018 | | NR |
Dan Ediger
|
|
|
spoke with Randy wip
|
PLM-Aging Inspection | 6/29/2018 | 6/29/2018 | 7/2/2018 | | NR |
Dan Ediger
|
|
|
wip
|
Plumbing Rough-in | 11/20/2017 | 11/21/2017 | 11/21/2017 | A | PART |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Powell. The sewer tie-in with a two way cleanout must be installed and inspected prior to final. The 3" vent stack must be exteded through the soffett for final rough-in inspection. The framer will build a soffett around it. OK to cover in the building.
|
Plumbing Rough-in | 11/15/2017 | 11/16/2017 | 11/16/2017 | P | FAIL |
Dan Ediger
|
|
|
open Phone #: ###-#### Inspection requested via web by Randy Powel Install a twoway cleanout at the sewer tie-in and test the sewer and graound-work. water ok
|