Final | 12/20/2018 | 12/21/2018 | 12/21/2018 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Paxman
|
Pressure Test | 12/6/2018 | 12/7/2018 | 12/7/2018 | A | PASS |
Eric Strole
|
|
|
Gas pressure test Phone #: ###-#### Inspection requested via web by Jeremy Paxman-20 lb gas test pass.
|
Pressure Test | 12/5/2018 | 12/6/2018 | 12/6/2018 | A | FAIL |
Eric Strole
|
|
|
Gas presure test Phone #: ###-#### Inspection requested via web by Jeremy Paxman-Need to use a 30 lb gauge for a 20 lb test and need 2 valves with an open tee in the middle when testing against a live system.
|