FIRE-Final Inspection | 7/2/2004 | 7/2/2004 | 7/2/2004 | A | PASS |
Rick Jackson
|
|
|
|
Letter of compliance | | | 7/2/2004 | | DONE |
|
|
|
Letter of Compliance issued 7-2-04.
|
FIRE-Conference | 6/15/2004 | 6/29/2004 | 6/29/2004 | P | PART |
Rick Jackson
|
|
|
Follow up for completion Project still under construction 6/29/2004 10:19:07 AM
|
FIRE-Conference | 5/5/2004 | 6/15/2004 | 6/15/2004 | P | PART |
Rick Jackson
|
|
|
Follow up to check status of the smoke/fire dampers and elevator smoke removal systems per agreement Talked to Brett and he said the equipment has been delayed and it should be completed within 2 weeks 6/15/2004 3:49:48 PM
|
FIRE-Final Inspection | 4/29/2004 | 4/30/2004 | 4/30/2004 | P | PART |
Rick Jackson
|
|
|
wendy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Final | 4/29/2004 | 4/30/2004 | 4/30/2004 | P | PART |
Dave Hannah
|
|
|
wendy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore all items completed but for two fire dampers hook up and elevator shaft venting 4/30/2004 4:39:52 PM
|
BLD-Conference | 4/27/2004 | 4/29/2004 | 4/29/2004 | A | DONE |
Dave Hannah
|
|
|
WENDY; Phone #: ###-#### Internet Inspection Request from: Annette Moore//PERMIT REOPENED PER DAVE HANNAH
|
FIRE-Conference | 4/27/2004 | 4/29/2004 | 4/29/2004 | A | PART |
Rick Jackson
|
|
|
WENDY; Phone #: ###-#### Internet Inspection Request from: Annette Moore//PERMIT REOPENED PER DAVE HANNAH Need plans for smoke ventilation of elevator shaft and smoke/fire damper operation on third floor; closure and smoke seals on rated doors 4/29/2004 10:16:49 AM
|
BLD-Conference | 4/27/2004 | 4/27/2004 | 4/27/2004 | P | CANC |
Dave Hannah
|
|
|
Permit reopened per Dave Hannah//RESCHEDULED FOR 04/29/04
|
CHANGE STATUS TO (ISS) | | | 4/27/2004 | | DONE |
|
|
|
permit reopened per Dave Hannah 04/27/2004
|
Fee Review-notes | 4/26/2000 | 4/26/2000 | 1/28/2004 | | DONE |
|
|
|
additional fees due from additional value from subs.
|
BLD-Conference | 9/17/2003 | 9/24/2003 | 9/24/2003 | A | CANC |
Dave Hannah
|
|
|
|
BLD-Conference | 9/17/2003 | 9/18/2003 | 9/18/2003 | A | DONE |
Dave Hannah
|
|
|
met with wendy talked about what needs to be finished with this permit 9/19/2003 9:55:16 AM
|
FIRE-Final Inspection | 9/15/2003 | 9/16/2003 | 9/16/2003 | A | PASS |
Rick Jackson
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
BLD-Final | 9/15/2003 | 9/16/2003 | 9/16/2003 | P | PART |
Dave Hannah
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
BLD-Conference | 6/16/2003 | 6/17/2003 | 6/17/2003 | P | PASS |
Carl Dependahl
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Annette Moore...complete restrooms; W.C. locations ok as discussed ... floor mount/rear discharge 6/17/2003 3:22:04 PM
|
Print Occupancy Form | | | 6/5/2003 | | DONE |
|
|
|
|
BLD-Conference | 5/5/2003 | 5/6/2003 | 5/6/2003 | P | PASS |
Carl Dependahl
|
|
|
Rick, re corridor upgrade.... 5/6/2003 3:25:55 PM
|
BLD-Conference | 4/9/2003 | 4/10/2003 | 4/10/2003 | P | PART |
Carl Dependahl
|
|
|
ele ok per J schmer 4/10/2003 2:38:49 PM
|
BLD-Conference | 3/31/2003 | 4/1/2003 | 4/1/2003 | A | PASS |
Carl Dependahl
|
|
|
Wendy...advised that permit req's final; consult/obtain plbg, elec, hvac and fire as needed. N&O isssued. 4/1/2003 8:54:35 AM
|
FIRE-Final Inspection | 4/30/2002 | 4/30/2002 | 4/30/2002 | P | PASS |
Troy Cobbley
|
|
|
fire life/safety finaled 4/30/2002 10:31:28 AM
|
Inspection Record Card- Bld | | | 4/30/2002 | | DONE |
|
|
|
|
FIRE-Final Inspection | 4/24/2002 | 4/24/2002 | 4/24/2002 | P | CANC |
Rick Jackson
|
|
|
###-#### TODD
|
BLD-Conference | 4/23/2002 | 4/23/2002 | 4/23/2002 | A | PASS |
Carl Dependahl
|
|
|
w/ Rick J...& Wendy, leasing agent...complete struct work for 3rd & 4th fl. upgrades; consult plbg re permits for req'd restrm. work. chk w/ elec insp for final for elec work associated w/ signage or alarms
|
BLD-Final | 4/22/2002 | 4/22/2002 | 4/23/2002 | P | NR |
Carl Dependahl
|
|
|
###-#### complete work for corridor & restroom upgrades 4/23/2002 10:35:24 AM
|
FIRE-Final Inspection | 4/22/2002 | 4/22/2002 | 4/22/2002 | P | FAIL |
Rick Jackson
|
|
|
early pm ###-#### need additional exit signs; will have to meet with Wendy and Carl about the list of agreement action items 4/22/2002 4:39:29 PM
|
BLD-Conference | 1/25/2002 | 1/25/2002 | 1/25/2002 | P | PASS |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 01/25/2002 at 10:38:32. Contact: ###-####...keep c/n re doors, corridor const, etc. consult plbg insp re ADA restrms/permits 1/25/2002 5:55:24 PM
|
BLD-Conference | 8/13/2001 | 8/13/2001 | 8/13/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/13/2001 7:40:50 AM w/ "new" contractor...status of...& to complete job; reinsp req'd.
|
Print Occupancy Form | | | 8/13/2001 | | DONE |
|
|
|
|
BLD-Conference | 8/8/2001 | 8/9/2001 | 8/9/2001 | A | PASS |
Carl Dependahl
|
|
|
call to meet there ###-####; w/ "new" contractor 8/9/2001 5:11:59 PM
|
(F) Reprint permit | | | 8/8/2001 | | DONE |
|
|
|
|
BLD-Conference | 7/23/2001 | 7/23/2001 | 7/23/2001 | P | PART |
Carl Dependahl
|
|
|
Conference on corridor requirements on 3rd flr. and accessibility requirements in restrooms.
|
FIRE-Final Inspection | 3/6/2001 | 3/7/2001 | 3/8/2001 | A | NR |
Rick Jackson
|
|
|
###-####
|
(F) Reprint permit | | | 3/8/2001 | | DONE |
|
|
|
|
BLD-Final | 3/6/2001 | 3/7/2001 | 3/7/2001 | A | FAIL |
Carl Dependahl
|
|
|
###-####, need all other signatures, complete remainder of c/n ... doors ,corridor walls sealed, etc3/7/2001 2:03:07 PM 3/7/2001 2:03:51 PM
|
BLD-Framing/Rough-in | 2/14/2001 | 2/14/2001 | 2/14/2001 | P | FAIL |
Carl Dependahl
|
|
|
###-####; c/n ...complete firestops, doors at corridors, seismic at ceilings, etc. 2/15/2001 11:43:47 AM
|
BLD-Conference | 2/14/2001 | 2/14/2001 | 2/14/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/14/2001 5:08:59 PM w/bldr re insps
|
Inspection Record Card- Bld | | | 2/6/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 2/6/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 2/6/2001 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 1/5/2001 | 1/5/2001 | 1/5/2001 | P | PART |
Carl Dependahl
|
|
|
###-#### r/i 4th fl r. rm wall ok 1/5/2001 6:08:57 PM
|
BLD-Conference | 12/6/2000 | 12/6/2000 | 12/6/2000 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 12/6/2000 4:27:06 PM w/ contractor re corridor upgrade, complete firestops, etc.
|
(F) Reprint permit | | | 10/31/2000 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 10/16/2000 | 10/16/2000 | 10/16/2000 | P | FAIL |
Jim Storey
|
|
|
4th floor Harry ###-#### c/n 2 hr floor ceilling pipe and chase areas/ wood in ceilling / old plasrer cilling removed is this part of thr old assembly.10/16/2000 4:12:05 PM 10/16/2000 4:15:24 PM
|
BLD-Conference | 9/13/2000 | 9/13/2000 | 9/13/2000 | P | PART |
|
|
|
Richard ###-#### pending arch submittals 9/14/2000 9:23:40 AM
|
Plan resubmittals received | | | 9/11/2000 | | |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM TAMURA AND ASSOCIATES TWO SETS OF SHEET A2.3, FORWARDED SAME TO PERRY PAINE.
|
(F) Reprint permit | | | 9/11/2000 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 6/27/2000 | | DONE |
|
|
|
|
Routing - FIRE | 5/17/2000 | 5/22/2000 | 5/22/2000 | | PASS |
Bill Alexander
|
|
|
|
Plan Review Completed(1st rev) | | | 5/22/2000 | | PASS |
Bill Alexander
|
|
|
|
Routing - PLAN CHECK | 5/22/2000 | | 5/22/2000 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/22/2000 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 5/22/2000 | | DONE |
|
|
|
|
Print Occupancy Form | | | 5/22/2000 | | DONE |
|
|
|
|
Telephone call | | | 5/22/2000 | | DONE |
|
|
|
talked to john price to verify plans are ready
|
Plan assigned to (CJW) | 5/2/2000 | | 5/22/2000 | | PASS |
Carl Westfall
|
|
|
5/22/00 15:25:21 CJW - activity updated through activity BLDA022 from case BLD00-01151.
|
Routing - PLAN CHECK | 5/3/2000 | | 5/16/2000 | | PASS |
|
|
|
|
Plan resubmittals received | | | 5/16/2000 | | PASS |
|
|
|
Received faxed resubmittal of new accessible toilet stall design.
|
Plan Reviewer's activity | | | 5/12/2000 | | PASS |
|
|
|
UBC plan review started May 12, 2000 and finished May 16, 2000. The drawings were approved with conditions. See the conditions list.
|
Routing - PUBLIC WORKS | 5/2/2000 | | 5/3/2000 | | DONE |
|
|
|
|
Pending Assignment by MYS | 5/2/2000 | | 5/2/2000 | | DONE |
Marlene Southard
|
|
|
|
Plan routing begun/TENANTS | | | 5/2/2000 | | DONE |
|
|
|
This plan is together with BLD00-01150 and so will be routed to PUBLIC WORKS, PLAN CHECK and FIRE.
|
Plan resubmittals received | | | 5/2/2000 | | DONE |
|
|
|
RECEIVED TWO SETS OF RESUBMITTALS FROM JOHN PRICE, ARCHITECT. SHEETS A0.0 AND SHEET 2.4. 5/2/00 DAR
|
Plans ACCEPTED BY PLAN TECH | | | 4/27/2000 | | DONE |
|
|
|
REQUESTED SUBMITTALS FROM JOHN PRICE PER CHECK-OFF LIST. 4/27/00
DAR
|
Application received | | | 4/26/2000 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/26/2000 | | DONE |
|
|
|
|
BLD-Final | 2/20/2001 | 2/20/2001 | 2/21/2000 | P | FAIL |
Carl Dependahl
|
|
|
###-####, c/n re doors, handrails; obtain other finals 2/21/2001 1:15:09 PM
|
BLD-Conference | 9/24/2003 | 9/25/2003 | | A | |
Dave Hannah
|
|
|
|