Permit Information
Permit NumberBLD03-02319
StatusFinaled
Name HEWLETT-PACKARD CO
Site Address 11311 W CHINDEN BLVD
Project NameHP #7 MFP TEST SPACE
Customer Number 
ePlanReviewNo
Description
(HP BLDG #7-1ST FLR)(MFP TEST SPACE) To remodel an existing 2,553 sq. ft. area for use as an 1,875 sq.ft. Test/Office area and 678 sq. ft. exit access / lobby, separated from surrounding areas by some walls and partial height movable partitions per approved plans. Work includes preparation of concrete floor for new cover, installation of new HVAC & electrical, installation of a new suspended grid ceiling system, upgrade of sprinkler and alarm systems to meet tenant needs & provide code compliance. Building is non-combustible, unprotected, fully sprinklered with 60 feet all around for unlimited area. PC03-588/drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Letter of compliance  8/11/2004 DONE
Letter of Compliance issued 8-11-04.
BLD-Final2/2/20042/3/20042/3/2004ACANC
DetailsJim Sly
Scheduled by a contractor via Hello! on 2/2/2004 at 2:09:29 PM. Contact: ###-####.
BLD-Final2/3/20042/3/20042/3/2004PPASS
DetailsJim Sly
Scheduled by a contractor via Hello! on 2/3/2004 at 9:18:03 AM. Contact: ###-####. OK for perm Occ. 2/3/2004 3:03:03 PM
BLD-Final1/30/20042/2/20042/2/2004PCANC
DetailsJim Sly
Scheduled by a contractor via Hello! on 1/30/2004 at 2:28:08 PM. Contact: ###-####.
FIRE-Final Inspection1/26/20041/28/20041/28/2004APASS
DetailsTroy Cobbley
fire alarm, fire sprinklers and fire life safety finaled 1/28/2004 8:40:49 AM
FIRE-Final Inspection1/26/20041/28/20041/28/2004APASS
DetailsTroy Cobbley
fire alarm, fire sprinklers and fire life safety finaled 1/28/2004 8:40:49 AM
FIRE-Alarm Testing1/27/20041/28/20041/28/2004ACANC
DetailsTroy Cobbley
duplicate inspection 1/28/2004 8:41:02 AM
FIRE-Alarm Testing1/27/20041/28/20041/28/2004ACANC
DetailsTroy Cobbley
duplicate inspection 1/28/2004 8:41:02 AM
Issue PAID IN FULL permit  11/7/2003 DONE
Inspection Record Card- Bld  10/27/2003 DONE
Permit Ready to Issue  10/27/2003 DONE
Telephone call  10/27/2003 DONE
Spoke with Katie Butler told permit ready & fees
Routing - PLAN CHECK10/24/2003 10/24/2003 PASS
Approved as noted on and the plan review conditions attached to a nd part of the approved drawings.
PLANS/APPL TAKEN TO FRONT DESK  10/24/2003 PASS
To permit desk to issue.
Plan assigned to (DRS)9/26/2003 10/24/2003 PASS
DetailsDan Stuart
10/24/2003 14:53:49 DRS - activity updated through activity BLDA022 from case BLD03-02319.
Routing - FIRE10/17/2003 10/24/2003 PASS
Telephone call  10/16/2003 DONE
Talked with Bob weber, Design Engineer at HP for mechanical plans & Mechanical energy compliance. we reviewed the outside air design data on the plan & the use of Tble. 403.3, 2000 IMC for certain occupant load per 1000 s.f rather than an occupant load factor and the difference it would make in his desin. I also review the exception for Table 404.1 containted in section 403.3 if statistical data is provide under his design stamp as and engineer if applicable. he will look at the exception and the table and determine what he will present for showing code compliance.
Telephone call  10/16/2003 DONE
Talked with John Hattan concerning data in lighting energy code compliance certificate and different values used within the same data. Will send me copy of ballast data used by designers to establish fixture wattage for code review.
Plan Reviewer's activity  10/16/2003 DONE
Received letter from mechanical engineer, Bob Weber, presenting his statistical data for use to determine outside air requirements per exception 403.3 versus Table 403.3. Table 403.3, based on the category chosen by Mr. Weber, would require the OA to be based on an occupant load of 153 for the area being remodeled. Mr. Weber designed the outside are requirements based on an occupant load of 43 per the IMC (used occ. load factor of 60 divided into 2,553 sq. remodel area = 43 x 20 = 860 cfm OA vs. 60 occupant per 1000 s.f. = 2.55 x 60 = 153 x 20 = 3,060 cfm OA required. Mr. Weber points out that the occupant load for the area based on work stations shown on plans is 24. He designed for 43 occ. load. almost twice what the designed work space will have. This space is also open to the adjoining spaces, separated only by 62" movable partitions already existing test areas.
I reviewed data with Marlene Southard explaining what is proposed & the common atmosphere with adjoining areas. We will accept the statisitcal dat from Mr. Weber based on the indicated occupant load and his professional status as a mechanical engineer. The request is stamped, signed and dated by Mr. Weber.
Routing - PLAN CHECK9/29/2003 10/16/2003 PEND
To fire code analyst for review. No resubmittals required.
Routing - PUBLIC WORKS9/26/2003 9/29/2003 PASS
Application received  9/24/2003  
Recd Pcfee & Taken To Pln CK  9/24/2003 DONE
Plans ACCEPTED BY PLAN TECH  9/24/2003 DONE
Fee Review-notes9/24/20039/24/2003