(F) Reprint permit | | | 1/30/2006 | | |
|
|
|
|
Second Notice BLD | 12/22/2005 | 12/22/2005 | 12/27/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 12/6/2005 | 12/22/2005 | | DONE |
|
|
|
|
Permanent occupancy | | | 12/6/2005 | | DONE |
|
|
|
Perm. Occ. Cert. # 10828 issued 12-6-05 to Western Trailers.
|
FIRE-Final Inspection | 12/2/2005 | 12/5/2005 | 12/5/2005 | A | PASS |
Forrest France
|
|
|
c/n items have been completed, fire life safety passed inspection.
|
Code Occupancy Approval | 11/15/2005 | 11/15/2005 | 11/15/2005 | A | DONE |
Dena Gambrel
|
|
|
Occupancy Inspection signed off.
|
FIRE-Final Inspection | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | FAIL |
Forrest France
|
|
|
See correction notice dated 11/14 for a listing of defficient items.
|
FIRE-Final Inspection | 11/14/2005 | 11/14/2005 | 11/14/2005 | P | FAIL |
Forrest France
|
|
|
Provide three 4A-10BC fire ext. not provided at this time, repair two emergency egress lights, door hardware is incorrect at office to shop area, provide key to knox box, provide fire dept. access signage at entry to supply way, need final on fire sprinklers prior to life safety signature.
|
FIRE-Final Inspection | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 11/9/2005 at 4:07:12 PM. Contact: ###-####.
|
FIRE-Final Inspection | 11/2/2005 | 11/3/2005 | 11/3/2005 | A | NR |
Forrest France
|
|
|
Fire sprinkler permit must be finaled prior to life safety sign-off.
|
BLD-Final | 11/2/2005 | 11/3/2005 | 11/3/2005 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 11/2/2005 at 3:46:50 PM. Contact: ###-####.final ok pending all other sign offs.
|
PubWorks Occupancy Approval | 11/3/2005 | 11/3/2005 | 11/3/2005 | | DONE |
|
|
|
Drainage project complete, signed permanent occupancy 11/03/05. R.Rokovitz
|
Permanent Occupancy | | 11/3/2005 | 11/3/2005 | | DONE |
|
|
|
|
BLD-Other | 10/26/2005 | 10/26/2005 | 10/26/2005 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/26/2005 at 9:48:44 AM. Contact: ###-####.ceilling ok
|
BLD-Framing/Rough-in | 9/16/2005 | 9/19/2005 | 9/19/2005 | A | PASS |
Jim Storey
|
|
|
|
BLD-Framing/Rough-in | 9/16/2005 | 9/16/2005 | 9/16/2005 | P | DEFR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 9/16/2005 at 11:03:39 AM. Contact: ###-####.out of time rollrd to monday.
|
CHANGE STATUS TO (ISS) | | | 9/14/2005 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 9/13/2005 | | 9/13/2005 | | PASS |
|
|
|
9/13/2005 14:05:37 JCM - activity updated through activity BLDA022 from case BLD05-00672.
|
Plan Reviewer's activity | | | 9/13/2005 | | PASS |
|
|
|
Reviewed and approved mezzanine level plan modification with red lined notes. JCM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/13/2005 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 9/13/2005 | | |
|
|
|
|
Inspection Record Card- Bld | | | 9/13/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 9/13/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/13/2005 | | DONE |
|
|
|
called ###-#### and left voicemessage for Melody that permit is ready and fees
|
Override - Parcel Holds | | | 9/13/2005 | | |
|
|
|
|
Permit Ready to Issue | | | 9/13/2005 | | |
|
|
|
|
Plan Modification Accepted | | | 9/12/2005 | | |
|
|
|
Plan modification accepted for BLD05-00672 for the redesign of mezzanine space. Original plan was approved with an open mezzanine with (1) small mechanical room in the corner of space. Appicant wishes to construct non-load bearing walls to create (3) offices in the mezzanine and the remainder of the sapce is to remain open. Received (3) copies of sheet A1.2. Routed to John M.
|
BLD-Aging Inspection | 8/12/2005 | 8/12/2005 | 8/12/2005 | | PASS |
Jim Storey
|
|
|
wip
|
Plan Reviewer's activity | | | 7/20/2005 | | DONE |
|
|
|
Talked to Gary Eichelberg at Design Resources and indicated that the proposed plan modification looked okay and requested that he submit a plan modification application and two sets of all plan sheets associated with the proposed modification. This conversation was based on a cover letter, dated July 11, 2005, and (2) 8 1/2"x11" plan sheet showing the proposed modification
|
BLD-Foundation | 6/3/2005 | 6/6/2005 | 6/6/2005 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 6/3/2005 at 10:45:37 AM. Contact: ###-####.
|
BLD-Footing | 5/31/2005 | 5/31/2005 | 5/31/2005 | P | PASS |
Mike Jordan
|
|
|
herb; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Extend Permit 180 days | 5/25/2005 | 5/26/2005 | 5/27/2005 | A | NR |
Jim Storey
|
|
|
|
BLD-Footing | 5/24/2005 | 5/25/2005 | 5/25/2005 | A | NR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 5/24/2005 at 11:30:56 AM. Contact: ###-####. rolled
|
(F) Reprint permit | | | 5/2/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/29/2005 | | DONE |
|
|
|
|
Routing - FIRE | 4/26/2005 | | 4/27/2005 | | PASS |
Bill Alexander
|
|
|
|
Routing - PLAN CHECK | 4/27/2005 | | 4/27/2005 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/27/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/27/2005 | | |
|
|
|
|
Inspection Record Card- Bld | | | 4/27/2005 | | |
|
|
|
|
Print Occupancy Form | | | 4/27/2005 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 3/15/2005 | | 4/27/2005 | | PASS |
|
|
|
4/27/2005 13:48:49 JCM - activity updated through activity BLDA022 from case BLD05-00672.
|
Routing - PLANNING | 4/25/2005 | | 4/26/2005 | | PASS |
|
|
|
Approved per DRH04-00298. Recorded agreement received 4/18/05 from attorney.
|
Routing - PLAN CHECK | 4/22/2005 | | 4/25/2005 | | PASS |
|
|
|
|
Plan resubmittals received | | | 4/22/2005 | | DONE |
|
|
|
Received Transmittal of Declaration of Access & Parking Easement Taken to John M.
|
Routing - FIRE | 4/19/2005 | | 4/22/2005 | | FAIL |
|
|
|
Did not respond to review Note 1A. Called architect to discuss, left message. Faxed review to architect.
|
Plan resubmittals received | | | 4/20/2005 | | DONE |
|
|
|
Resubmittals received and forwarded to John M.: 2 copies of plan sheets A7.2
|
Plan resubmittals requested | | | 4/19/2005 | | DONE |
|
|
|
Faxed the architect a letter requesting additional revisions. JCM
|
Routing - PLAN CHECK | 4/1/2005 | | 4/19/2005 | | FAIL |
|
|
|
|
Plan resubmittals received | | | 4/18/2005 | | |
|
|
|
Received (2) copies of revised sheets - Cover; Civil C1.0-C1.6; Architectural A0.1,A0.2,A1.1,A1.2,A2.1,A3.1,7.1,A7.2; Plumbing P1.1.
|
Plan resubmittals requested | | | 4/5/2005 | | DONE |
|
|
|
Faxed the architect a comment list requesting additional revisions for the construction documents. JCM
|
Plan resubmittals received | | | 4/4/2005 | | DONE |
|
|
|
Resubmittals received and forwarded to John M.: 1 copy of small docs info from MOJ Engineering (marked "Preliminary Drawing"), and 2 copies of plan sheets cover, A1.2, A2.1, A3.1, A7.1, A7.2 and M1.2.
|
1st review completed | | | 4/1/2005 | | FAIL |
|
|
|
failed planning, plan check and fire.
|
Routing - FIRE | 3/28/2005 | | 4/1/2005 | | FAIL |
|
|
|
lacks FD access, req'd FH's, fire flow and sprinkler flow, haz mat and exiting info; proper fire alarm design. Review faxed to architect.
|
Routing - PLANNING | 3/25/2005 | | 3/28/2005 | | FAIL |
|
|
|
DRH04-00298 Sara S.
Waiting for a copy of a recorded access/egress easement for the property. I contacted Ryan with Design Resources (Rocky was not available). I will keep the plans routing so that I don't hold up the review process while the document is being created.
|
Routing - PLAN CHECK | 3/28/2005 | | 3/28/2005 | | FAIL |
|
|
|
John M.
|
Plan resubmittals requested | | | 3/28/2005 | | DONE |
|
|
|
Mailed the architect a copy of the plan review requesting revisions. JCM
|
Routing - PLUMBING | 3/23/2005 | | 3/25/2005 | | PASS |
|
|
|
Lavies required to meet UPC 414.1
Approved per plan and 2003 UPC
|
Routing - Erosion and Sediment | 3/22/2005 | | 3/23/2005 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing - PUBLIC WORKS | 3/18/2005 | | 3/22/2005 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 3/17/2005 | | 3/18/2005 | | PASS |
|
|
|
Lot 1, Block 1, Supply Way Park Subdivision
|
Plans ACCEPTED BY PLAN TECH | | | 3/16/2005 | | |
|
|
|
This Project went Green Tag 3-16-05 Called Ryan 3-16-05 need new Civil Sheets ASAP . Waiting for call back..
|
Plan routing begun/NEW & ADDTN | | | 3/16/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 3/15/2005 | | DONE |
|
|
|
|
Application received | | | 3/14/2005 | | |
|
|
|
|