Information based on query as of Friday, September 27, 2024.
Permit Information
Permit NumberBLD06-02052
StatusFinaled
Name KREIZENBECK CONSTRUCTORS
Site Address 251 E FRONT ST Unit: 305
Project NameONE FRONT ST-3RD FLR
Customer Number 
ePlanReviewNo
Description
Kreizenbeck Constructors RCE # 764 (NO TENANT - VANILLA FINISH)(ONE FRONT STREET - STE 305) This building is fully sprinklered as substitution for 1-hour fire resistive construction. There is an existing 1-hour rated corridor connecting the 2-hour stair enclosures that serve as the exits for all tenants on this floor. To build-out interior finishes for a NEW "VANILLA" FINISH space of 2,884 sq. ft. for proposed future office.The remainder of this floor is occupied by Edam & Burke. Work includes non-combustible framing & furr out around columns and stair enclosure; non-combustible framed partitions to create rooms & areas for future reception, conference and open office. To perform work on electrical, mechanical, plumbing, sprinkler and alarm systems to comply with current adopted codes and ordinances of Boise City. To modify a section of the existing rated corridor to relocate & install a new 20 minute fire rated, smoke and draft control, self closing, door and frame as the new entry door and install a 45 minute fire rated glazed sidelite and frame. Install a suspended ceiling grid system, diffusers and light fixtures and finish interior walls of "Vanilla" space for a future, yet to be determined tenant. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD2/12/20072/12/20079/25/2015 DONE
DetailsCathy Chiles
This permit finaled on the web by Brandon Byington
Second Notice BLD2/2/20072/2/20072/12/2007 DONE
First Notice has not been responded to.
First Notice1/18/20071/18/20072/2/2007 DONE
DetailsDave Hannah
Letter of compliance  1/25/2007 DONE
Letter of Compliance issued 1-25-07
BLD-Final1/17/20071/18/20071/18/2007APASS
DetailsDave Hannah
erin; Phone #: ###-#### Internet Inspection Request from: Darla Downs
DOC - Permit Finaled1/18/20071/18/20071/18/2007PPASS
DetailsDave Hannah
FIRE-Final Inspection1/15/20071/16/20071/16/2007APASS
DetailsForrest France
Fire life safety inspection is satisfactory.
BLD-Other11/16/200611/17/200611/17/2006PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/16/2006 at 5:51:10 PM. Contact: ###-####.ceiling grid ok to cover
BLD-Other11/16/200611/17/200611/16/2006ACANC
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/16/2006 at 9:50:53 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Nov 16 2006 5:56PM.
BLD-Framing/Rough-in10/9/200610/10/200610/10/2006APART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 10/9/2006 at 12:16:05 PM. Contact: ###-####. walls ok to cover
Issue PAID IN FULL permit  9/13/2006 DONE
Inspection Record Card- Bld  8/29/2006 DONE
Telephone call  8/29/2006 DONE
tlk to cindy ###-#### that permit and fees are ready to be picked up but needs GC/RCE #
Permit Ready to Issue  8/29/2006 DONE
Plan assigned to (DRS)7/19/2006 8/28/2006 PASS
8/28/2006 16:25:00 DRS - activity updated through activity BLDA022 from case BLD06-02052.
Routing - FIRE8/21/2006 8/28/2006 PASS
Attached review comments to plans.
1st review completed  8/28/2006 PASS
Routing - PLAN CHECK8/28/2006 8/28/2006 PASS
To permit desk to issue.
PLANS/APPL TAKEN TO FRONT DESK  8/28/2006 PASS
Telephone call  8/21/2006 DONE
Called Hal Whipple, TW Engineering concerning need for Mech com check and outside air requirements and details for supplying the same for this tenant improvment Vanilla Finish. He will send me the data today and I will attach to plans.
Telephone call  8/21/2006 DONE
Called Glancey-Rockwell Architects concerning need for 45 minute fire rated glazing in the new sidelite shown on plans in the existing rated corridor wall. I talked with Cindy. shee will follow up with addendum & contractor and I will red-line on the plans.
Routing - PLAN CHECK7/20/2006 8/21/2006 PEND
No resubmittals required. Plans red-lined with attached plan review clarifications. Routing to fire code analyst for review.
Routing - PUBLIC WORKS7/19/2006 7/20/2006 PASS
Application received  7/18/2006  
Recd Pcfee & Taken To Pln CK  7/18/2006  
Plans ACCEPTED BY PLAN TECH  7/18/2006