Permit Information
Permit NumberBLD08-02169
StatusFinaled
Name ARTISAN BUILDERS
Site Address 11624 W PRESIDENT DR
Project NameENVIRO-TECH INC
Customer Number 
ePlanReviewNo
Description
(ENVIRO-TECH INC) **PLAN MODIFICATION PER THE APPROVED PLANS DATED 12/19/2008. ADDITION OF FULLY ACCESSIBLE MEZZANINE RESTROOM, ADDITION OF EXTERIOR DOOR AND SECOND STAIR FROM MEZZANINE, RECONSTRUCTION OF EXISTING STAIRWAY, CLARIFICATION OF FIRE-RATED OVERHEAD DOOR FRAME CONSTRUCTION. (SRZ)** Remodel to an existing tenant space. This building is not fire sprinklered. Work to include: demolish some existing non-bearing interior walls and a portion of an interior partition divider, install new exterior high windows with electric awnings on the east and west walls, repair sheetrock, paint, repair/install new trim, remove some existing plumbing fixtures, install new restroom, install walls and door for new compressor room, and install new drinking fountains. All work per approved plans, plan review report, and with all applicable codes and ordinances. CZC08-00155 **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 10/31/200911/5/2009 DONE
DetailsBarbara Stitt
Second Notice 9/28/200910/21/2009 DONE
DetailsBarbara Stitt
First Notice3/4/20093/4/20099/17/2009 DONE
DetailsMike Jordan
BLD-Final3/3/20093/4/20093/4/2009APASS
DetailsMike Jordan
Scheduled by a contractor via Hello! on 3/3/2009 at 4:41:53 PM. Contact: ###-####.
DOC - Permit Finaled3/4/20093/4/20093/4/2009PPASS
DetailsMike Jordan
ok for perm. occ.
BLD-Final2/25/20092/25/20092/25/2009PPART
DetailsMike Jordan
Rod- call 30 mins prior to going Phone #: ###-####. will be ok for final once plumbing has finaled. ok to move stuff in.
FIRE-Final Inspection2/24/20092/25/20092/25/2009APASS
DetailsTroy Cobbley
life safety passed. Contractor to remove the exit sign that is located in the shop but directs people to the locked door to the front offices. Sam the plan reviewer was ok with this due to seven other exits.
FIRE-Final Inspection2/19/20092/20/20092/20/2009APART
DetailsTroy Cobbley
The inspection today was just for the fire door which upon the second try and an adjustment worked correctly. Signage has not been provided yet.
FIRE-Final Inspection2/18/20092/18/20092/18/2009AFAIL
DetailsTroy Cobbley
See the city approved plans for locations of the deficiencies that include non-approved door hardware, inoperative exit signs and emergency lights. None of the exit discharge lights appear to have been installed. Also the new fire door fusible links have not been installed as per NFPA 80 and the door has not been tested/witnessed by the fire inspector.
Zoning Approval2/18/20092/18/20092/18/2009 PASS
DetailsJosh Wilson
OK per CZC08-00155
BLD-Final2/17/20092/17/20092/17/2009PCANC
DetailsMike Jordan
Rod Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
FIRE-Final Inspection2/17/20092/17/20092/17/2009PCANC
DetailsTroy Cobbley
rod Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
BLD-Footing1/12/20091/13/20091/13/2009APASS
DetailsMike Jordan
rod Note: for slap for star lading Phone #: ###-####
Telephone call  1/12/2009 DONE
DetailsSam Zahorka
Spoke with Chris the contractor and answered his questions. He stated the owner is not installing the roof fans and not completeing the upper mezzanine bathroom. Main floor cabinets are required to be no more then 34" in hgt. Upper mezzanine has no accessible route or accessible means of egress required. Cabinets and sink are allowed to be over 34". Future permit will be required to finish bathroom in future. SRZ
BLD-Framing/Rough-in1/6/20091/6/20091/6/2009PPASS
DetailsMike Jordan
Rod Phone #: ###-####. Framing for new overhead fire door and installation of remainder of existing 2hr. fire barrier wall ok. Also reviewed resubmitted and approved plans.
BLD-Framing/Rough-in12/30/200812/31/200812/31/2008APART
DetailsJim Sly
ROD Phone #: ###-####
Framing OK for restroom at mezzanine.....Infill at existing rated firewall where ductwork was removed.....OK to install final layer.
Plan assigned to (SRZ)12/24/200812/24/200812/29/2008 PASS
DetailsSam Zahorka
12/29/2008 11:00:33 SRZ - activity updated through activity BLDA022 from case BLD08-02169.
Routing - PLAN CHECK12/24/2008 12/29/2008 PASS
DetailsSam Zahorka
PLANS/APPL TAKEN TO FRONT DESK  12/29/2008 DONE
Routing - Erosion and Sediment12/29/2008 12/29/2008 PASS
DetailsSam Zahorka
ESC Review-Low Risk. Nothing required per Form #707.
CHANGE STATUS TO (ISS)  12/29/2008 DONE
plan mod picked up and plan put to issue ///DLD
(F) Reprint permit  12/29/2008 DONE
Case Summary (BLD)  12/24/2008 DONE
DetailsSam Zahorka
CHANGE STATUS TO (REV)  12/24/2008 DONE
DetailsAlexandra L. DeYoung
Plan Modification Accepted  12/24/2008 DONE
DetailsAlexandra L. DeYoung
Plan Mod rec'd for clarififcation of fire-rated overhead door frame construction, reconstruction of mezzanine stair, addition of exterior door & stair from mezzanine, and addition of mezzanine level restroom- three copies of sheets 1-5
Plan Reviewer's activity  12/23/2008 DONE
DetailsSam Zahorka
Recieved fax from the Architect for plan modification. No plans recieved though. Called applicant and architect left message.
BLD-Framing/Rough-in12/11/200812/11/200812/11/2008PPART
DetailsMike Jordan
rod Phone #: ###-####. fur out wall for new plumbing pipes ok.
BLD-Conference12/4/200812/5/200812/5/2008ADONE
DetailsMike Jordan
Meeting with contractor,architect and overhead door installer at 10:00am. Met on site with contractor, architect and dorr installer. Went over issues listed on c/n. Architect to provide revised drawings and submit to plan review.
BLD-Conference12/3/200812/4/200812/4/2008AFAIL
DetailsMike Jordan
Provide additional drawings and details for additional duct openings in firewall and show that openings including new fire door do not exceed 25%. Also provide UL listing and detailsfor thru penetrations. Also provide details on how openings are to be protected. Provide UL listing and details for jamb installation on fire door. Fire door is not in line with 2hr. fire wall, provide detail showing fire door in line with firewall or for continuation of jamb protection. Also provide details for code compliant stairway to mezz. Also noted that mezz may be used as breakroom, this is not shown on approved plans. If so, provide aditional details showing code compliant mezz and exiting. Also need to provide calcs to see if in place floor framing will support floor loads for breakroom or storage as is anticipated. Plans must be submitted to pland review for approval before any further work in these areas can proceed.
BLD-Conference12/4/200812/4/200812/4/2008ACANC
DetailsMike Jordan
Meeting with contractor, architect and overhead door installer at 10:00am.
BLD-Framing/Rough-in12/3/200812/3/200812/3/2008PPART
DetailsMike Jordan
Fireblocking and stud shoes added at framing for tumbler room. Also noted that mezz wants to be used as a breakroom, this is not shown on approved plans. Existing stairway is non compliant and mezz is enclosed, 2nd exit may be required. A conferance has been set up in am. A c/n on non compliant items will be issued at that time.
BLD-Framing/Rough-in12/2/200812/3/200812/3/2008AFAIL
DetailsMike Jordan
rod Phone #: ###-####. Needs to provide fireblocking at furred space at tunbler room and provide some stud shoes. Also noted uprotected openings in 2hr. fire wall. Noted to contracted that I would contact plan review and investigate further to see what needs to be done.
Telephone call  11/12/2008 DONE
Details
t/c w james gipson at ###-#### - permit ready and fees given
Permit Ready to Issue  11/12/2008 DONE
Details
Issue PAID IN FULL permit  11/12/2008 DONE
Routing - PLAN CHECK11/3/2008 11/10/2008 PASS
DetailsSam Zahorka
Case Summary (BLD)  11/10/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  11/10/2008 DONE
DetailsSam Zahorka
Inspection Record Card- Bld  11/10/2008 DONE
Details
Plan assigned to (SRZ)10/11/2008 11/10/2008 PASS
DetailsSam Zahorka
11/10/2008 15:58:54 SRZ - activity updated through activity BLDA022 from case BLD08-02169.
Routing - FIRE10/31/2008 11/3/2008 PASS
DetailsScott Arellano
Attached updated IFC comments to plans
Plan resubmittals received  11/3/2008  
DetailsSam Zahorka
Received 1 response letter dated 10-31-08 to Sam Z from James Gipson, 1 copy of overhead door series 600 specs, 2 copies of sheet 2 and taken to San Zahorka's desk///11-3-08 @ 12:10pm BAS
Routing - PLAN CHECK10/28/2008 10/31/2008 FAIL
DetailsSam Zahorka
2nd plan review comment/correction emailed to the architect.
Plan resubmittals received  10/31/2008 DONE
received transmittal letter from james gipson asso. & (2) pages of comments from james gibson---"2" sets of plans with (2) sheets each of 1, 2, 3, & 5--plans taken to Sam Zahorka
Plan resubmittals received  10/31/2008  
DetailsSam Zahorka
Rec'd one response letter, and two copies of sheets 2, 3 and 5; taken to Sam Z
Routing - FIRE10/24/200810/24/200810/28/2008 FAIL
DetailsScott Arellano
Faxed and emailed resubmittal items to architect.
Plan resubmittals received  10/28/2008  
DetailsSam Zahorka
Rec'd one response letter, and 2 copies of pages 1 & 2; and taken to Sam Z.
1st review completed  10/28/2008 FAIL
Failed Plan Check, Fire
Route to Impact Fee Review10/27/200810/30/200810/27/2008 PASS
DetailsCindy M. Gould
Tenant improvement no impact fees
Routing - PLAN CHECK10/13/2008 10/27/2008 FAIL
DetailsSam Zahorka
Emailed Plan Review comments to Architect. Routed to Fire.
Routing PW Environmental10/15/2008 10/15/2008 PASS
DetailsWalt Baumgartner
OK, facility inspected for pretreatment requirements 10/14/08
Routing - Design Review10/13/2008 10/13/2008 PASS
DetailsAndrea Tuning
Approved per CZC08-00155
Routing PW Sewer Rating10/13/2008 10/13/2008 PASS
DetailsLouise Waldorf
Routing - PUBLIC WORKS10/11/2008 10/13/2008 PASS
DetailsBeverly Hall
Pending Assignment by JCB10/9/2008 10/11/2008 DONE
DetailsJason Blais
Plans ACCEPTED BY PLAN TECH  10/10/2008 DONE
DetailsAlexandra L. DeYoung
Recd Pcfee & Taken To Pln CK  10/10/2008 DONE
DetailsAlexandra L. DeYoung
Zoning Approval2/17/20092/17/2009   
DetailsAndrea Tuning
Application received 10/9/2008   
DetailsAlexandra L. DeYoung