ePlanReview 
Description
Electrical Permit - Alteration: Upsize service and wire printing press
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice Sent 2/1/20052/17/2005 DONE
This permit finaled on the web by Jim Williams
DOC - Permit Finaled2/1/20052/1/20052/1/2005PPASS
DetailsJack Frank
Finaled by inspector at 2/1/2005 12:42:20 PM
Final2/1/20052/1/20052/1/2005PPASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Jim Williams ok listing for press and corrections made 2/1/2005 12:42:12 PM
Electrical Rough-In1/31/20051/31/20051/31/2005APART
DetailsJack Frank
conference ok
Final1/28/20051/28/20051/28/2005PFAIL
DetailsJack Frank
kim ; Phone #: ###-#### Internet Inspection

Request from: Marsha Smylie cor. posted called, 300.10 bond bushing for REwashers, 314.28, shall provide required distance between raceways, as code noted states, 250.148 tag equip grd to boxes, power for press red taged and turned off,

asked owner frist if press power could be turned off he said yes ETL testing did not follow Boise City process for field testing
1/28/2005 5:00:41 PM 1/28/2005 5:01:11 PM
Permanent Service12/19/200412/20/200412/20/2004APASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Jim Williams needs 2 grd rods size bonding to 250.66, remove sprinkler equip from below p/s
p/s u/g rec. ok 12/20/2004 8:28:52 AM
Application received  12/16/2004  
This permit was created on the web by Jim Williams