Third Notice ELE | 4/21/2005 | 4/21/2005 | 4/29/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 4/11/2005 | 4/11/2005 | 4/21/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 4/1/2005 | 4/11/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 4/1/2005 | 4/1/2005 | 4/1/2005 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 4/1/2005 1:17:01 PM
|
Final | 4/1/2005 | 4/1/2005 | 4/1/2005 | P | PASS |
Jack Frank
|
|
|
per jack frank--john ###-#### okcard signed 4/1/2005 1:16:58 PM
|
Final | 3/31/2005 | 3/31/2005 | 3/31/2005 | P | PART |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/o ok card signed 3/31/2005 2:20:01 PM
|
Final | 3/29/2005 | 3/30/2005 | 3/30/2005 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/29/2005 at 3:26:10 PM. Contact: ###-####. cor. posted called 314.23(D)(2)&300.11(A) support boxes and cables, 330.30(B&C) & 300.11 support cables and raceways 358.30(A) 400.8(5) no cords above ceiling, 314.27(D) listed fan boxes needed, seal opening in sub panel, 3/30/2005 11:32:35 AM
|
Rough-In Permanent Service | 2/23/2005 | 2/24/2005 | 2/24/2005 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/23/2005 at 12:49:05 PM. Contact: ###-####. r/i ok
p/s o/h new ok 2/24/2005 10:00:38 AM
|
Electrical Rough-In | 2/3/2005 | 2/3/2005 | 2/3/2005 | P | PART |
Jack Frank
|
|
|
wall cover insp doug; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 2/3/2005 4:02:39 PM
|
Application received | | | 1/13/2005 | | |
|
|
|
|
Issue permit | | | 1/13/2005 | | DONE |
|
|
|
|