Temporary Service | 3/2/2005 | 3/3/2005 | 3/3/2005 | A | PASS |
Bob Reichert
|
|
|
kim ###-#### called contr, left survey, 110.26 orient pole so work space shall be maintained, 352.30(A) support strap shall be provided. t/s u/g n ok 3/3/2005 8:42:01 AM
|
DOC - Permit Finaled | 3/3/2005 | 3/3/2005 | 3/3/2005 | A | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 3/3/2005 8:42:04 AM
|
Temporary Service | 3/1/2005 | 3/2/2005 | 3/2/2005 | A | FAIL |
Bob Reichert
|
|
|
Kim; Phone #: ###-#### Internet Inspection Request from: Jan Rice 406.4(D) recpt shall project from faceplate, 406.8(B)(2) recpt shall use in-use cover, 310.12(C) ungrounded conductors shall not be white, BCC job id sticker shall be posted. Re-nspection fee due. called contr , left corr notice. 3/2/2005 10:16:57 AM
|
Issue permit | | | 3/1/2005 | | DONE |
|
|
|
|
Application received | | | 3/1/2005 | | |
|
|
|
|