Final | 11/14/2005 | 11/14/2005 | 11/14/2005 | P | PASS |
Jack Frank
|
|
|
ok owner secured contractor to wire hot tub
|
Final | 9/15/2005 | 10/13/2005 | 10/13/2005 | A | NH |
Jim Schmer
|
|
|
stopped to see if hot tub still there, no access, left card
|
Final | 9/14/2005 | 9/15/2005 | 9/16/2005 | A | FAIL |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 9/14/2005 at 9:21:30 PM. Contact: ###-####. resched final for 9/19/05 370 & 412 did an inspection & would not release the service because we did not the home owner working in a hot panal fixing the corrections
|
Permanent Service | 9/15/2005 | 9/15/2005 | 9/15/2005 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 9/14/2005 at 9:21:30 PM. Contact: ###-####. p/s o/h reconnect ok
|
Permanent Service | 9/14/2005 | 9/14/2005 | 9/14/2005 | P | FAIL |
Jack Frank
|
|
|
all violations not corrected met with owner he needs to secure electrical contractor , all he wants to do is argue GEC conductors not nterminated to neutral bus, needs to ID neutral needs connectors for GEC, needs to install 2 grd rods he put bond bushings on PVC conduit
|
Conference | 9/13/2005 | 9/13/2005 | 9/13/2005 | P | FAIL |
Jack Frank
|
|
|
chad-- call 1st before insp cell ###-#### cor. posted met owner , owner shall correct all wiring done without permit, and secure electrical contractor to secure permit for hot tub, remove all wiring he installed for hot tub, it is all mwssed up, 334.15(B) romex exposedin patio, 344.22 use proper size rmc for wire fill, 250.92(A) bond nipple between meter and p/s,250.52,104,66 size, bond hot and cold, grd to u/g water pipe, 250.64 conn for GEC, 250.53,56 needs 2 grd rods, 230.24(A) 8ft over roof for clearence, 300.21 remove panel from warm wall
|
Application received | | | 9/13/2005 | | |
|
|
|
|
Issue & PRINT permit | | | 9/13/2005 | | |
|
|
|
|