ELE-Aging Inspection | 12/14/2009 | 12/14/2009 | 12/17/2009 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 12/17/2009 | 12/17/2009 | 12/17/2009 | A | PASS |
Jack Frank
|
|
|
no action for over 1 year
|
Permanent Service | 11/20/2008 | 11/21/2008 | 11/21/2008 | A | PASS |
Bob Reichert
|
|
|
KEN nOTE: PLEASE CALL 15 MIN PRIOR TO INSPECTION Phone #: ###-#### p/s u/g n ok
|
Permanent Service | 11/17/2008 | 11/17/2008 | 11/17/2008 | P | CANC |
Mike Kinnear
|
|
|
ken - please call 1/2 hr prior Phone #: ###-#### wrong type of inspection
|
Conference | 11/17/2008 | 11/17/2008 | 11/17/2008 | P | DONE |
Mike Kinnear
|
|
|
ken - please call 1/2 hr prior Phone #: ###-#### needs proper staples & romex connectors that can handle more than romex cable. he is to put 4inch of concrete over under ground conduit before final.
|
Electrical Rough-In | 7/31/2008 | 8/1/2008 | 8/1/2008 | A | PASS |
Mike Kinnear
|
|
|
ken Phone #: ###-#### ok cover ri
|
Electrical Rough-In | 7/28/2008 | 7/29/2008 | 7/29/2008 | A | FAIL |
Bob Reichert
|
|
|
ken Phone #: ###-#### met owner ,corrections 300.4(A)&(D) shall provide 1 1/4" for bored holes and nm cable from face of framing member, 300.14 shall provide 6" free conductor length in boxes, 110.12(C) there shall be no broken boxes, NOTE: ok to cover concrete encased electrode, owner found rebar to tie to
|
Conference | 1/4/2006 | 1/6/2006 | 1/6/2006 | A | DONE |
Jack Frank
|
|
|
ken -call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
|
Application received | | | 1/4/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 1/4/2006 | | |
|
|
|
|