Final | 1/30/2006 | 1/30/2006 | 1/30/2006 | P | PASS |
Bob Reichert
|
|
|
corrections requested by Bob Reichart performed; Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s o/h reconnected, ok to final
|
Final | 1/27/2006 | 1/30/2006 | 1/30/2006 | A | FAIL |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see ps
|
Permanent Service | 1/27/2006 | 1/30/2006 | 1/30/2006 | A | FAIL |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 250.56 A single electrode shall be augmented by 1 additional electrode, 6' apart., 408.4 circuit directory shall be provided, 210.52(A)(1) shall use metal water pipe within 5' of bldg as grounding electrode
|
Application received | | | 1/26/2006 | | DONE |
|
|
|