Final | 6/29/2006 | 6/29/2006 | 6/29/2006 | P | PASS |
Jack Frank
|
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok also ok for dirt cover of electrode
|
Electrical Rough-In | 6/23/2006 | 6/23/2006 | 6/23/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung r/i ok electrode ok for concrete cover only, called needs to terminate GEC and steel bond to equip grd bus not neutral and remove bond screw
|
Rough-In Permanent Service | 6/22/2006 | 6/22/2006 | 6/22/2006 | P | FAIL |
Jack Frank
|
|
|
dhad; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called left message,110.3(B) and 225.36 needs main at garage, needs concrete encased electrode, 200.6 shall not ID 6 or smaller neutral, 300.4(D) 11/4"parallel to framing members, 410.4(A) needs fixture approved for outside, BCC remove devices from boxes so I can inspect, 250.104(C) bond building steel
|
Electrical Rough-In | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | PART |
Jack Frank
|
|
|
###-#### - ed Note: underground ok
|
Issue permit | | | 6/15/2006 | | DONE |
|
|
|
|
Application received | | | 6/15/2006 | | |
|
|
|
|