Temporary Service | 8/3/2006 | 8/4/2006 | 8/4/2006 | A | PASS |
Pat Lass
|
|
|
Internet Inspection Request from: Latisha Peltier T/S O/H Ok
|
Temporary Service | 8/3/2006 | 8/3/2006 | 8/3/2006 | P | CANC |
Pat Lass
|
|
|
Internet Inspection Request from: Latisha Peltier Inspection cancelled from web by: Latisha Peltier
|
Temporary Service | 8/2/2006 | 8/2/2006 | 8/2/2006 | P | FAIL |
Bob Reichert
|
|
|
overhead service; new construction Internet Inspection Request from: Latisha Peltier called contr, left corr notice, nec 406.8(B) recepts shall have a weatherproof cover whether or not a plug is inserted, 408.38 panelboard shall be deadfront, 110.12(A) unused openings shall be closed
|
Application received | | | 8/2/2006 | | DONE |
|
|
|
This permit was created on the web by Latisha Peltier
|