Second Notice ELE | 5/14/2007 | 5/14/2007 | 5/21/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 4/20/2007 | 4/20/2007 | 5/14/2007 | | DONE |
William E Thomas
|
|
|
|
Final | 4/19/2007 | 4/20/2007 | 4/20/2007 | A | PASS |
William E Thomas
|
|
|
jeremy - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith final ok
|
Final | 3/22/2007 | 3/23/2007 | 3/23/2007 | A | FAIL |
Jack Frank
|
|
|
jeremy Note: please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called fee due 400.8(2&5) cord shall not pass through ceiling, support all cables in area where work was done above grid ceiling
|
Reinspection Fee (no hold) | 3/23/2007 | 3/23/2007 | 3/23/2007 | P | DONE |
Jack Frank
|
|
|
jeremy Note: please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles fee due prior corr. not made
|
Conference | 3/2/2007 | 3/9/2007 | 3/9/2007 | A | DONE |
Bob Reichert
|
|
|
jeremy - ###-#### - pls call prior to inspection - bill thomas told r/p to have inspection request routed to bob mert contr and bldr to review violations and corrections, will fix and recall. At this point, clean up grid in new dental care ceiling violations, rest ok.
|
Conference | 3/1/2007 | 3/2/2007 | 3/2/2007 | P | DONE |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 3/1/2007 at 5:18:41 PM. Contact: ###-####.
|
Final | 3/1/2007 | 3/2/2007 | 3/2/2007 | P | CANC |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 3/1/2007 at 5:14:25 PM. Contact: ###-####.
|
ELE-Aging Inspection | 11/13/2006 | 11/13/2006 | 11/15/2006 | | CANC |
Jack Frank
|
|
|
|
Final | 9/12/2006 | 9/13/2006 | 9/13/2006 | P | FAIL |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, told to call inspector, asking for final, ri not given yet, need to look at x-ray equipment, is metal piping installed? Are violations present? Will need to meet contractor at job. Left correction notice from failed ri inspection request as posted.
|
Electrical Rough-In | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | FAIL |
Bob Reichert
|
|
|
jeremy; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left message, nec 517.13(A) metal raceways shall be provided for grounding purposes, BCC no violations shall be retained, Note: partial corrections until rest of equipment opened up
|
Application received | | | 8/24/2006 | | |
|
|
|
|
Issue permit | | | 8/24/2006 | | DONE |
|
|
|
|