Permanent Service | 6/29/2007 | 6/29/2007 | 6/29/2007 | P | FAIL |
Bob Reichert
|
|
|
nicki Phone #: ###-#### met owner, left corr notice, nec 250.52(A)(1) shall connect metal water pipe as grounding electrode,250.53(D)(2) shall provide supplemental grounding electrode per 250.56, 110.3(B) shall use listed clamps, 110.12(C) there shall be no deteriorated parts, BCC shall provide minimum 2" mast with proper clearances, told owner several options for service, he has to install and we will inspect
|
Permanent Service | 1/19/2007 | 1/22/2007 | 1/22/2007 | A | NR |
Bob Reichert
|
|
|
Niki ###-####n called and explained vertical clearance requirements over patio, service disconnect, and grounding requirements. Suggested either home-owner fix or talk with electrical contractor.
|
Application received | | | 1/19/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 1/19/2007 | | DONE |
|
|
|
|