Final | 7/31/2007 | 7/31/2007 | 7/31/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/31/2007 at 5:30:57 AM. Contact: ###-####. called, left message, 1 outlet with rev polarity , ok to final
|
Rough-In Permanent Service | 5/21/2007 | 5/21/2007 | 5/21/2007 | P | CANC |
Bob Reichert
|
|
|
rowdy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type inspection request, see ri
|
Electrical Rough-In | 5/21/2007 | 5/21/2007 | 5/21/2007 | P | PASS |
Bob Reichert
|
|
|
rowdy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made, ric ok
|
Permanent Service | 5/21/2007 | 5/21/2007 | 5/21/2007 | A | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Electrical Rough-In | 5/21/2007 | 5/21/2007 | 5/21/2007 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/21/2007 at 6:09:19 AM. Contact: ###-####. called, left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 nm cable shall not be stapled on edge,BCC boxes shall be installed and make-up done
|
Application received | | | 5/16/2007 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|