Final | 9/5/2007 | 9/6/2007 | 9/6/2007 | A | PASS |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James reviewed potting with contr, able to see thru water, ok to final
|
Final | 8/27/2007 | 8/28/2007 | 8/28/2007 | A | FAIL |
William E Thomas
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James 1. needs to have a potting compound inspection.
|
Electrical Rough-In | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | PART |
Jack Frank
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James; swimming pool bonding e grid and diving board and handrails ok
|
Electrical Rough-In | 8/8/2007 | 8/9/2007 | 8/9/2007 | A | PASS |
Bob Reichert
|
|
|
mike Note: inground goduit inspection Phone #: ###-#### u/g raceways only ok to cover, corrections made
|
Electrical Rough-In | 8/7/2007 | 8/7/2007 | 8/7/2007 | P | FAIL |
Bob Reichert
|
|
|
mike - swimming pool conduit Phone #: ###-#### called, left corr notice, left message, nec 300.5 raceways shall be 18" deep to top of conduit, 352.26 rnc shall not have over 360 degree total bends between pull points, BCC shall see all u/g before cover
|
Electrical Rough-In | 7/27/2007 | 7/27/2007 | 7/27/2007 | P | PASS |
Bob Reichert
|
|
|
mike - swimming pool; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang pool bond and u/g length of pool only ok to cover
|
Application received | | | 7/27/2007 | | |
|
|
|
|
Issue permit | | | 7/27/2007 | | DONE |
|
|
|
|