Final | 1/28/2008 | 1/28/2008 | 1/28/2008 | P | PASS |
Bob Reichert
|
|
|
Casey ###-#### ok to final
|
Electrical Rough-In | 11/15/2007 | 11/16/2007 | 11/16/2007 | A | PASS |
Bob Reichert
|
|
|
casey Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 11/15/2007 | 11/15/2007 | 11/15/2007 | P | FAIL |
Jack Frank
|
|
|
casey Phone #: ###-#### all violations not corrected 250.148 grd all metal boxes, 300.4(D), 11/4" cables parallel, also jbox ceiling laundry rm shall be accessible, 334.23 protect cables within 6ft attic access, energy code shall use air tight cans
|
Electrical Rough-In | 11/13/2007 | 11/14/2007 | 11/14/2007 | A | FAIL |
Bob Reichert
|
|
|
casey Phone #: ###-#### called owner, left correction notice, nec 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members (both sides), 300.4(F) shall provide insulating bushing for ser cable at sub-panel, 250.86 sahll provide and wire ground screw in metal box
|
Conference | 10/2/2007 | 10/2/2007 | 10/2/2007 | P | DONE |
Bob Reichert
|
|
|
CASEY Phone #: ###-#### talked about new addition, outlet spacing, afci breakers, when to come for ri inspection
|
Application received | | | 9/7/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/7/2007 | | DONE |
|
|
|
|