ELE-Aging Inspection | 5/13/2010 | 5/13/2010 | 5/18/2010 | | DONE |
Bob Reichert
|
|
|
see doc expire
|
DOC - Permit Expired | 5/18/2010 | 5/18/2010 | 5/18/2010 | A | PASS |
Bob Reichert
|
|
|
no activity, ok to doc expire
|
Rough-In Permanent Service | 4/23/2008 | 4/24/2008 | 4/24/2008 | A | PASS |
Pat Lass
|
|
|
key to padlock is in the back of the house in an old ammunissions box. Phone #: ###-#### Internet Inspection Request from: David Nelson R/I OK P/S O/H R Ok
|
Electrical Rough-In | 4/23/2008 | 4/24/2008 | 4/23/2008 | A | CANC |
Pat Lass
|
|
|
key to padlock is in back of house in old ammunissions box. Phone #: ###-#### Internet Inspection Request from: David Nelson Inspection cancelled from web by: David Nelson
|
Electrical Rough-In | 4/18/2008 | 4/21/2008 | 4/21/2008 | A | FAIL |
Jack Frank
|
|
|
Key to unlock padlock is in the back of the house in an old ammunissions box. Phone #: ###-#### Internet Inspection Request from: David Nelson called corr. 210.52(A) outlet wall space right of bath rm door in din rm 300.5 24" for uf in trench, 312.5 (C) needs conn for cables remove cables from raceways, also remove GEC from jbox and raceways, 334.15 protect exposed cables in basement, 250.148 grd bell boxes, note update permit for garage p/s and 1 rm also attach ELE to BLD permit
|
Application received | | | 4/14/2008 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|