First Notice | 9/3/2008 | 9/3/2008 | 3/3/2009 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/2/2008 | 9/3/2008 | 9/3/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jenni Keller ok to final, signed structural card
|
Final | 8/4/2008 | 8/5/2008 | 8/5/2008 | P | PART |
Jack Frank
|
|
|
Final For Childrens Store Phone #: ###-#### Internet Inspection Request from: Jenni partail only needs show window recepts
|
Final | 8/4/2008 | 8/5/2008 | 8/4/2008 | A | CANC |
Bob Reichert
|
|
|
Final Electrical Inspection for childrens store Phone #: ###-#### Internet Inspection Request from: Jenni Keller Inspection cancelled from web by: Jenni Keller
|
Electrical Rough-In | 7/10/2008 | 7/10/2008 | 7/10/2008 | P | PASS |
Bob Reichert
|
|
|
Re-inspection Phone #: ###-#### Internet Inspection Request from: Jenni Keller corrections made, ok to cover walls only to divide stores
|
Electrical Rough-In | 7/9/2008 | 7/10/2008 | 7/10/2008 | A | FAIL |
Bob Reichert
|
|
|
Partial Rough-in, Courtesy Inspection? Phone #: ###-#### Internet Inspection Request from: Jenni Keller called contractor, left correction notice, NEC 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members
|
Owner Supplied Equipment | | | 6/16/2008 | | |
|
|
|
|
Application received | | | 6/16/2008 | | DONE |
|
|
|
This permit was created on the web by Jenni Keller
|
Second Notice ELE | 3/3/2009 | 3/3/2009 | | | |
|
|
|
First Notice has not been responded to.
|