Final | 12/3/2008 | 12/4/2008 | 12/4/2008 | A | PASS |
Pat Lass
|
|
|
garage code is 7100 Phone #: ###-#### Internet Inspection Request from: Cevyn Recla
|
Rough-In Permanent Service | 9/29/2008 | 9/29/2008 | 9/29/2008 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla ok cover ri p/s u/g reconnect ok corrections made
|
Rough-In Permanent Service | 9/25/2008 | 9/25/2008 | 9/25/2008 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called all violations not corrected
|
Rough-In Permanent Service | 9/23/2008 | 9/23/2008 | 9/23/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called left correction notice, NEC 110.12(B) panel shall not be damaged, nor cable over sub-panel, 334.30 shall secure ser by approved means and also nm in up bath shall be secured witin 12 of box, 210.52(E)(1) shall provide receptacle at front of dwelling, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member-kitchen,BCC shall provide box for range, shall remove sub-panel from closet
|
Application received | | | 9/17/2008 | | DONE |
|
|
|
This permit was created on the web by Cevyn Recla
|