DOC - Permit Expired | 5/25/2010 | 5/25/2010 | 5/25/2010 | A | PASS |
Jack Frank
|
|
|
work has been taken over by new owner's contr
|
ELE-Aging Inspection | 5/25/2010 | 5/25/2010 | 5/25/2010 | | CANC |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 3/19/2010 | 3/19/2010 | 3/22/2010 | | CANC |
Jack Frank
|
|
|
|
Conference | 10/7/2008 | 10/8/2008 | 10/8/2008 | A | DONE |
Bob Reichert
|
|
|
Please meet Brian Keith at Property at 9 a.m. Wednesday. Thanks. Phone #: ###-#### Internet Inspection Request from: Clint Tate met contractor to review requirements to bring park up to code, no esc this project
|
Permanent Service | 10/6/2008 | 10/6/2008 | 10/6/2008 | P | FAIL |
Bob Reichert
|
|
|
met electrician, left correction notice, NEC 230.24(B) (4) service drop conductors shall be 18' over road, 344.30(A) shall rigidly support conduit within 3' of termination, 312.5 shall provide abrasion protection for all conductors entering enclosures,(meters), 110.26 shall provide work space about equipment, ref 550 mobile home parks, BCC shall inspect all u/g before cover, no violations shall be retained, no esc this project
|
Permanent Service | 10/3/2008 | 10/6/2008 | 10/6/2008 | A | CANC |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Clint Tate 370 needs to do this inspection
|
Application received | | | 10/1/2008 | | DONE |
|
|
|
This permit was created on the web by Clint Tate
|