First Notice | 5/19/2009 | 5/19/2009 | 3/4/2015 | | DONE |
Jack Frank
|
|
|
This permit finaled on the web by ron spen cer
|
Final | 5/18/2009 | 5/19/2009 | 5/19/2009 | A | PASS |
Jack Frank
|
|
|
ron Phone #: ###-#### ok card signed
|
Final | 5/15/2009 | 5/18/2009 | 5/18/2009 | A | NR |
Jack Frank
|
|
|
Ron Phone #: ###-#### called needs gfci for commercial kit all 120V
|
Final | 5/14/2009 | 5/15/2009 | 5/15/2009 | A | FAIL |
Jack Frank
|
|
|
Ron Phone #: ###-#### no access called
|
Reinspection Fee (no hold) | 5/15/2009 | 5/15/2009 | 5/15/2009 | A | PASS |
Jack Frank
|
|
|
Ron Phone #: ###-#### no access
|
Permanent Service | 5/5/2009 | 5/5/2009 | 5/5/2009 | P | PASS |
Jack Frank
|
|
|
ron - please call 1/2 prior or around 1:00 pm Phone #: ###-#### p/s o/h rec. ok
|
Conference | 4/13/2009 | 4/13/2009 | 4/13/2009 | P | DONE |
Jack Frank
|
|
|
question on more than one service to building called contr left nessage, note house and resturant are one building , art. .230 states only one p/s allowed
|
Permanent Service | 4/10/2009 | 4/10/2009 | 4/10/2009 | P | FAIL |
Jack Frank
|
|
|
insp on moving the sub panel//Ron ###-#### see added r/i
|
Electrical Rough-In | 4/10/2009 | 4/10/2009 | 4/10/2009 | P | FAIL |
Jack Frank
|
|
|
insp on moving the sub panel//Ron ###-#### 314.28(A)(2) shall provide 6X for raceway entries at jbox, 310.16 shall not use $ copper for 100 amp commercial job,200.6&7 shall not ID 6 or smaller neutral shall be white, shall ID neutral used as phase in cables, 250.148 shall terminate all equip. grds to jbox (old panel)BCC no vilations retained grding and bonding at p/s shall meet article 250, also 110.3(B) manufactures instructions use manufactures listed breakers only called left message
|
Application received | | | 4/10/2009 | | |
|
|
|
|
Issue & PRINT permit | | | 4/10/2009 | | DONE |
Tisha Gallop
|
|
|
|