Final | 8/5/2010 | 8/5/2010 | 8/5/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, ok final
|
Rough-In Permanent Service | 6/21/2010 | 6/22/2010 | 6/22/2010 | A | PASS |
Bob Reichert
|
|
|
Neil Phone #: ###-#### called, corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/21/2010 | 6/21/2010 | 6/21/2010 | P | DONE |
Bob Reichert
|
|
|
Neil Phone #: ###-#### met contractor, corrections NEC 3334.23 shall protect cables within 6' of attic access, 300.4(D) shall provide nailplates, BCC shall box nm cable where terminates in bath
|
Application received | | | 6/21/2010 | | |
|
|
|
|
Issue permit | | | 6/21/2010 | | DONE |
Barbara Stitt
|
|
|
|