Final | 7/9/2010 | 7/9/2010 | 7/9/2010 | A | PASS |
Bob Reichert
|
|
|
Bob the trench is deeper and we have wired the irrigation pump. Any questions please give me a call ###-#### Thanks Shaun Inspection requested from web by: Shaun Kirkman Phone #: ###-#### ok cover u/g. ok to final
|
Electrical Rough-In | 7/7/2010 | 7/7/2010 | 7/7/2010 | P | CANC |
Bob Reichert
|
|
|
trench has been dug deeper for conduit Inspection requested from web by: Shaun Kirkman Phone #: ###-#### contractor called and wants to reschedule after pump installed
|
Rough-In Permanent Service | 7/2/2010 | 7/2/2010 | 7/2/2010 | P | CANC |
Bob Reichert
|
|
|
richard Phone #: ###-#### see ri and p/s
|
Electrical Rough-In | 7/2/2010 | 7/2/2010 | 7/2/2010 | P | FAIL |
Bob Reichert
|
|
|
richard Phone #: ###-#### called gave correction notice, NEC 300.5 u/g for pvc shall be 18" deep, not 12"
|
Electrical Rough-In | 7/2/2010 | 7/2/2010 | 7/2/2010 | P | FAIL |
Bob Reichert
|
|
|
richard Phone #: ###-#### called gave correction notice, NEC 300.5 u/g for pvc shall be 18" deep, not 12"
|
Permanent Service | 7/2/2010 | 7/2/2010 | 7/2/2010 | P | PASS |
Bob Reichert
|
|
|
richard Phone #: ###-#### p/s o/h n ok
|
Application received | | | 7/2/2010 | | |
|
|
|
|
Issue permit | | | 7/2/2010 | | DONE |
|
|
|
|