First Notice | 10/8/2010 | 10/8/2010 | 11/22/2010 | | DONE |
Bob Reichert
|
|
|
|
Final | 10/7/2010 | 10/8/2010 | 10/8/2010 | A | PASS |
Bob Reichert
|
|
|
steve Phone #: ###-#### ok final, signed card
|
Electrical Rough-In | 9/20/2010 | 9/20/2010 | 9/20/2010 | P | PASS |
Jack Frank
|
|
|
George-Ceiling inspection for a drop ceiling please Phone #: ###-####
|
Electrical Rough-In | 8/3/2010 | 8/3/2010 | 8/3/2010 | P | PART |
Jack Frank
|
|
|
George Phone #: ###-#### walls ok called still needs all branch circuits feeding patient care areas shall be redundent back to the panel feeding them
|
Electrical Rough-In | 8/2/2010 | 8/2/2010 | 8/2/2010 | P | FAIL |
Jack Frank
|
|
|
George Phone #: ###-#### corr. nail plates and 11/4" for cables and ent parallel to studs, strap cables 12" of boxes, 517.13 A&B medical grade cable for patient care areas note switches and homeruns to panels
|
Application received | | | 8/1/2010 | | DONE |
|
|
|
This permit was created on the web by George Pascua
|