Final | 12/16/2010 | 12/17/2010 | 12/17/2010 | A | PASS |
Jack Frank
|
|
|
MIKE Phone #: ###-#### ok card signed
|
Final | 12/15/2010 | 12/15/2010 | 12/15/2010 | P | FAIL |
Bob Reichert
|
|
|
mike Phone #: ###-#### called, left correction notice, NEC 725.25 shall remove abandoned low voltage cables, 300.11 cables and raceways shall not be supported by ceiling grid or tiles, BCC shall install seismic wires for fixtures, no violations shall be retained
|
Electrical Rough-In | 12/7/2010 | 12/7/2010 | 12/7/2010 | P | PASS |
Bob Reichert
|
|
|
Mike Phone #: ###-#### ri ok
|
Application received | | | 12/7/2010 | | |
|
|
|
|
Issue & PRINT permit | | | 12/7/2010 | | DONE |
Barbara Stitt
|
|
|
|
First Notice | 12/17/2010 | 12/17/2010 | | | |
Jack Frank
|
|
|
|