Permanent Service | 12/22/2010 | 12/22/2010 | 12/22/2010 | P | PASS |
Jack Frank
|
|
|
Jared. Phone #: ###-#### >> Inspection requested via web by joel smith p/s o/h rec. ok
|
Final | 12/22/2010 | 12/22/2010 | 12/22/2010 | P | PASS |
Jack Frank
|
|
|
Jared. Phone #: ###-#### >> Inspection requested via web by joel smith
|
Permanent Service | 12/21/2010 | 12/21/2010 | 12/21/2010 | P | FAIL |
Jack Frank
|
|
|
Jared Phone #: ###-#### >> Inspection requested via web by joel smith called violation not corrected
|
Permanent Service | 12/20/2010 | 12/20/2010 | 12/20/2010 | P | FAIL |
Jack Frank
|
|
|
Jared- electrician. Phone #: ###-#### >> Inspection requested via web by joel smith corr. posted called service drop shall not be above weatherhead 230.54(C)
|
Electrical Rough-In | 12/20/2010 | 12/20/2010 | 12/20/2010 | P | PASS |
Jack Frank
|
|
|
Jared- electrician. Phone #: ###-#### >> Inspection requested via web by joel smith ok to cover u/g conduit
|
Permanent Service | 12/17/2010 | 12/17/2010 | 12/17/2010 | P | FAIL |
Bob Reichert
|
|
|
Jared is the electrician. Phone #: ###-#### >> Inspection requested via web by joel smith called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 300.5 direct burial shall be 24" deep, 230.24(A) service conductors shall be 8' over roof surface, BCC shall post job id sticker, shall post address, NOTE shall locate ground rods
|
Application received | | | 12/16/2010 | | DONE |
|
|
|
This permit was created on the web by joel smith
|